PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Determination of the equivalent magnetic characteristic of the cores of TPZ class protective current transformers

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Metoda obliczania zastępczej charakterystyki magnesowania rdzeni przekładników zabezpieczeniowych klasy TPZ
Języki publikacji
EN
Abstrakty
EN
A method of computation of the equivalent magnetic characteristic of the cores with air gaps applied in a TPZ class protective current transformer is presented in this paper. The effective total length of the air gaps determined based on this characteristics permits on accuracy estimation the property of the protective current transformer. The analysis was performed for cores with different number and length of air gaps. The field distributions in cores with air gaps were analysed based on the field-and-circuit method. Some computational results were compared with test results.
PL
W artykule przedstawiono metodę obliczania zastępczej charakterystyki magnesowania rdzeni, zawierających szczeliny powietrzne, stosowanych w przekładnikach zabezpieczeniowych klasy TPZ. Na podstawie tej charakterystyki można dokładnie określić długość zstępczej szczeliny powietrznej, a tym samym dokładnie określić właściwości metrologiczne przekładnika na etapie projektowania. Analiza została przeprowadzona dla rdzeni o różnej liczbie i długości szczelin. Rozkłady pola magnetycznego w rdzeniach ze szczelinami powietrznymi zostały wyznaczone przy zastosowaniu metody numerycznej polowo-obwodowej. Wykonano badania dla różnych typów rdzeni przekładników i przy różnym prądzie wymuszającym. Porównano również otrzymane metodą polowo-obwodową wyniki z wynikami badań na modelach fizycznych.
Rocznik
Strony
123--126
Opis fizyczny
Bibliogr. 9 poz., rys., wykr.
Twórcy
  • Politechnika Łódzka, Katedra Elektrotechniki Ogólnej i Przekładników, ul. Stefanowskiego 18/22, 90-924 Łódź, elalesni@p.lodz.pl
Bibliografia
  • [1] E. Lesniewska, Applications of the Field Analysis During Design Process of Instrument Transformers, Transformers in Practice, Vigo Spain 2006, pp.227-251
  • [2] Biddlecombe C.S., Simkin J., Jay A.P., Sykulski J.K., Lepaul S., Transient Electromagnetic Analysis Coupled to Electric Circuit and Motion, IEEE Transactions on Magnetics, vol.34, no 5, 1998, 3182-3185
  • [3] E. Lesniewska and W. Jalmuzny, Influence of the Number of Core Air Gaps on Transient State Parameters of TPZ Class Protective Current Transformers, accepted for publication in IET Science, Measurement & Technology, 2009, Vol. 3, No. 2, pp. 105–112
  • [4] W. W. Afanasiew, and et al., Current Transformers, Energoatomizdat, Leningrad, 1989 (in Russian)
  • [5] W. Jałmużny, D. Adamczewska, I. Borowska-Banaś, Simulation Method of Metrology Assessment of Transient Performance Current Transformers (in Polish), Pomiary Automatyka Kontrola, no 10bis/2006, pp. 96-101
  • [6] A. Koszmider, J. Olak and Z. Piotrowski, Current Transformers, WNT, Warsaw, 1985 (in Polish)
  • [7] E. Lesniewska and J. Ziemnicki, Transient State Analysis of Protective Current Transformers at Different Forced Primary Currents, Przegląd Elektrotechniczny 5’2006, pp. 57-60
  • [8] E. Lesniewska, Application of Electromagnetic Field Simulations in the Design Process of Instrument Transformer, Zeszyty Naukowe PŁ, nr 766, Rozprawy Naukowe z.236, 1997 (in Polish)
  • [9] Instrument transformers – Part 6: Requirements for protective current transformers for transient performance, International Standard IEC 60044-6:1992, modified
Typ dokumentu
Bibliografia
Identyfikator YADDA