PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Powiadomienia systemowe
  • Sesja wygasła!
  • Sesja wygasła!
Tytuł artykułu

Voltage/current control mode for combined three-phase inverter

Autorzy
Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Sterowanie napięciem i prądem w równoległym systemie przekształtników trójfazowych
Języki publikacji
EN
Abstrakty
EN
For parallel inverters system, controlling the output voltage in normal operation constantly is named the voltage control mode (VCM), and controlling the output current constantly in abnormal operation conditions (such as short circuit) is named the current control mode (CCM). The combined three-phase inverter topology is presented, the equivalent inverter topology with a LCL filter is obtained and mathematical models are built in VCM and CCM. A hybrid control strategy is proposed. The PID control and the repetitive control are used in VCM to obtain the fast dynamic responses and low harmonic distortions. On the other hand, the state feedback control is used in CCM. Pole assignment has been employed in designing parameter of the PID controller and state feedback, and the repetitive control design process is given. Experimental results validate the proposed control using two 400KVA parallel inverters.
PL
Dla równoległego systemu przekształtników zazwyczaj stosuje się system kontroli napięcia VCM i system kontroli prądu CCM (w warunkach specjalnych - np. zwarcia). Zaprezentowano topologie przekształtnika trójfazowego. Odpowiednia topologia przekształtnika z filtrem LCL została przedstawiona. Zaproponowano hybrydową strategię sterowania. System PID sterowania użyty w VCM zapewnia szybką odpowiedź dynamiczną i małe zniekształcenia. W układzie CCM użyto stałego sprzężenia zwrotnego. Sprawdzono położenie biegunów. Wyniki eksperymentu z dwoma 400kVA równoległymi przekształtnikami potwierdziły założenia.
Rocznik
Strony
358--362
Opis fizyczny
Bibliogr. 9 poz., rys.
Twórcy
autor
autor
autor
autor
Bibliografia
  • [1] Wang H., Yue X., Pei X., A hardware and software current limit protection strategy for the combined three-phase inverter,Transactions of China Electro technical Society., 23(2008), No. 9, 92-97
  • [2] Guerrero J M., De Vicuna L G., Matas J., A wireless controller to enhance dynamic performance of parallel inverters in distributed generation systems,IEEE Trans.Power Electron., 19(2003),No. 5,1205-1213
  • [3] Guerrero J M., De Vicuna L G., Matas J., Output impedancje design of parallel-connected UPS inverters with wireless loadsharing control,IEEE Trans.Ind.Electron.,52(2005),No.4, 1126-1135
  • [4] Erika T., Holmes D G., Grid current regulation of a three-phase voltage source inverter with an LCL input filter,IEEE Trans. Power Electron.,18(2003), No. 5, 888-895
  • [5] Fei L., Yan Z., Shanxu D., Parameter design of a two-currentloop controller used in a grid-connected inverter system with LCL filter,IEEE Trans.Ind.Electron.,56(2009),No.11,4483-4491
  • [6] Shen G., Xu D., Xi D., An improved control strategy for gridconnected voltage source inverters with a LCL filter,IEEE Trans. Power Electron.,23(2008), No. 4,1899–1906
  • [7] Zhang K., Kang Y., Xiong J., Direct Repetitive Control of SPWM Inverter for UPS Purpose, IEEE Trans. Power Electron., 18(2003), No.5, 784-792
  • [8] Zhang B., Wang D., Zhou K., Linear phase lead compensation repetitive control of a CVCF PWM inverter,IEEE Trans. Ind.Electron., 56(2008), No. 4,1595-1602
  • [9] Hou T., Pei X., Liu M., The uniform control scheme of high power combined three-phase inverter,Proceedings of the CSEE., 26(2006), No. 25, 63-67
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-article-BPOB-0046-0013