PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

International comparison of AC current ratio standards

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Międzynarodowe porównanie wzorców stosunku prądów przemiennych
Języki publikacji
EN
Abstrakty
EN
This paper presents the results of an international comparison of AC current ratio standards between the Czech Metrology Institute (CMI) and the Georgian National Agency for Standards, Technical Regulation and Metrology (GEOSTM). Ratio errors and phase displacements were measured in the range (5 up to 2 000) A at 50 Hz mains frequency. Two GEOSTM 2-stage standard current transformers were used as transfer standards. These transformers were designed and developed at GEOSTM Tbilisi, Georgia.
PL
W artykule przedstawiono międzynarodowe porównanie wzorców stosunku prądów AC wykonanych przez Czeski Instytut Metrologii CMI i Gruzińską Narodową Agencję Wzorców, Norm i Metrologii GEOSTIM. Zbadano błąd stosunku oraz fazy w zakresie 5 - 2000 A przy częstotliwości 50 Hz. Wykorzystano wzorce Instytutu gruzińskiego. Transformatory zostały opracowane w GEOSTM.
Rocznik
Strony
252--256
Opis fizyczny
Bibliogr. 8 poz., rys., tab.
Twórcy
autor
  • Czech Technical University in Prague, Faculty of Electrical Engineering, Department of measurement, Technická 2, CZ-166 27 Prague 6 - Dejvice, Czech Republic., draxler@fel.cvut.cz
Bibliografia
  • [1] W. J.M.Moore, P.N.Miljanic : The Current Comparator. Peter Peregrinus Ltd. 1988. ISBN 0 863411126
  • [2] S.Harmon, L .Henderson: Final report EUROMET.EMS11 on EUROMET Projects 473 and 612: Comparison of the measurement of current transformers (CTs).
  • [3] K.Draxlr, R.Styblíková, W.Waldman, A.Jakab: International Comparison of AC Current Ratio Standards 50 Hz. Proc. of the XVI IMEKO World Congress, Vienna 2000. Vol. V, pp. 247 – 252.
  • [4] K.Draxler, R.Styblíková: Interlaboratory Comparison of Instrument Current Transformer Standards in the Range up to 800 A at 50 Hz. Proc. of XI IMEKO TC4 Symposium, Lisbon 2001, Vol. 2, pp. 466-470.
  • [5] E.-P.Suomalainen, J.K.Hallstrom: Onsite Calibration of a Current Transformer Using a Rogowski Coil. IEEE Transaction, Vol. 58, Issue 4, April 2009, pp. 1054-1058, ISSN: 0018-9456.
  • [6] R.Styblíková, K.Draxler, M.Šimůnek: System for Checking of Automatic Instrument Transformer Test Sets. Proc. Of the XIV IMEKO WORLD CONGRESS, Tampere, Finland, Volume IVB, pp.75 - 80.
  • [7] R.Styblíková, K.Draxler, N.Lobjanidze: Bilateral comparison of current ratio standards. Draft A. April 2010.
  • [8] BIPM, IEC, IFCC, ISO, IUPAC, IUPAP, OIML, Guide to the Expression of Uncertainty in Measurement, International Organization for Standardization, Geneva, First Edition 1993.