Prostownik diodowy z dławikami sprzężnymi i małym równoległym filtrem aktywnym
Języki publikacji
Abstrakty
The article describes the laboratory and simulation tests of 12- and 24- pulse power grid converter systems with DC voltage output that work together with shunt active power filter (APF). It presents both the operations' principles and the results of these tests. The systems under discussion make it possible to reduce the number of unwanted higher harmonics in the power network current. Moreover, they can also help eliminate the 23- and 25-order harmonics especially in the conditions of local power network supply. In order to obtain the multipulsed system's operation, a set of coupled three-phase power network reactors (CTR) has been used.
Artykuł zawiera wyniki badań symulacyjnych i testów laboratoryjnych 12- i 24- pulsowego przekształtnika sieciowego z wyjściowym obwodem napięcia stałego, pracującego z równoległym filtrem aktywnym. Omówione rozwiązanie pozwala znacząco zredukować występowanie niepożądanych harmonicznych prądu sieci, tym całkowicie wyeliminować harmoniczne rzędu 23 i 25. Wielopulsowa praca układu została osiągnięta poprzez zastosowanie zespołu trójfazowych dławików sprzężonych.
Rocznik
Tom
Strony
5--16
Opis fizyczny
Bibliogr. 11 poz.
Twórcy
Bibliografia
- [1] Aredes M., 1996. Active Power Line Conditioners. The doctor engineer dissertation, Technical University of Berlin.
- [2] Depenbrock M., 1990. A new 18-pulse rectifier circuit with line-side interphase transformer and nearly sinusoidal line currents, IAS.
- [3] Miyairi S., 1986. New method for reducing harmonics involved in input and output of rectifier with interphase transformer. IEEE Trans. on Ind. Aplic.
- [4] Mysiak P., 1996. The DC-output multipulse converter in the low voltage power network supply conditions (in polish). The doctors thesis dissertation, Warsaw Technical University.
- [5] Mysiak P., 2005. A multi-pulse diode rectifier with a coupled three-phase reactor – the design method and results of the simulation and laboratory tests. Electrical Power Quality and Utilisation Journal XI(1), ISSN 1234-6799.
- [6] Supronowicz H., Strzelecki R., 2000. The power factor in AC-power supplying systems and its improvement methods (in polish). Publishing House of Warsaw Technical University.
- [7] Tunia H., Barlik R., Mysiak P., 1998. The coupled reactors system for current higher harmonics reducing in three-phase loads supplying from VSI (in polish). Electrical Power Quality and Utilisation, Cracow.
- [8] Wojciechowski D., 2005. Novel estimator of distorted and unbalanced electromotive force of the grid for control system of PWM rectifier with active filtering. EPE 2005, Dresden.
- [9] Wojciechowski D., 2006. Grid voltages sensorless control of PWM rectifier with active filtering. Electrical Power Quality and Utilisation Journal XII(1), 43-48, ISSN 1234-6799.
- [10] Akagi H., Watanabe E.H., Aredes M., 2007. Instantaneous power theory and applications to power conditioning. John Wiley&Sons.
- [11] Strzelecki R., Supronowicz H., 1997/1999. Filtration of the harmonic in AC supply systems (in Polish). Adam Marszałek Publishing House, ed.1/ed.2, Poland 215 p.
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-article-BAT1-0041-0033