Study on the Influence of Test Methods on AC and DC Pollution Flashover Performance of Different UHV Insulators

Autorzy
Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Badanie odporności izolatora UHV na przeskoki AC i DC wynikające z zanieczyszczeń – porównanie wpływu metod badawczych na wynik
Języki publikacji
EN
Abstrakty
EN
This paper presents the flashover performance of three different insulators by using different test method. The results show that the influence of test method on the flashover performance of polluted insulators is significant. The average flashover voltage Uav obtained by evenraising the voltage method is 6.2% to 10.7% higher than the 50% breakdown voltage U50 obtained by the up-and-down method. The results also reveal a slight difference of pollution exponents obtained by different method which analyzed theoretically based on the Obenaus model.
PL
W artykule przedstawiono porównanie odporności trzech typów izolatorów na zjawisko przeskoku, przy pomocy różnych metod badawczych. Wykazano duży wpływ rodzaju zastosowanej metody na wynik analizy przy występujących zanieczyszczeniach. Stwierdzono także różnice w znaczeniu zanieczyszczeń w modelu, w zależności od metody.
Rocznik
Strony
166--170
Opis fizyczny
Bibliogr. 12 poz., schem., tab., wykr.
Twórcy
autor
  • College of Electrical Engineering, Chongqing University, Chongqing 400044, China
autor
  • College of Electrical Engineering, Chongqing University, Chongqing 400044, China
autor
  • College of Electrical Engineering, Chongqing University, Chongqing 400044, China
autor
  • College of Electrical Engineering, Chongqing University, Chongqing 400044, China
autor
  • College of Electrical Engineering, Chongqing University, Chongqing 400044, China
Bibliografia
  • [1] Lambeth P. J., Schneider H. M., Beausejour Y., Cherney E. A., Dumora D., Kawamura T., Marrone G., Moran J. H., Naito K., Nigbor R. J., Sakich J. D., Stearns R., Tempelaar H., Verma M. P., Huc J., Perin D., Johnson G. B., De Ligt C., Final Report on the Clean Fog Test for HVAC Insulators. IEEE Trans. Power Deliv., 2 (1987), 1317-1326
  • [2] Baker A. C., Farzaneh M., Gorur, R. S., Gubanski S. M., Hill R. J., Karady G. G., Schneider H. M., Insulator Selection for AC Overhead Lines With Respect to Contamination. IEEE Trans. Power Deliv., 24 (2009),1633-1641
  • [3] Dela O A., Gorur R. S., Burnham J. T., Electrical performance of non-ceramic insulators in artificial contamination tests. Role of resting time, IEEE Trans. Diele. Elect. Insul., 3 (1996), 827-835
  • [4] Xingliang, J., Lichun, S., Caixin, S, Contamination and icing Insulation of power system, China Electric Power Press: Beijing, 2009
  • [5] Dela O, A., Gorur, R. S., Flashover of contaminated nonceramic outdoor insulators in a wet atmosphere. IEEE Trans. Diele. Elect. Insul., 5 (1998), 814-823
  • [6] Karady, G. G., Flashover mechanism of non-ceramic insulators, IEEE Trans. Diele. Elect. Insul., (6) 1999, 718-723
  • [7] Schneider, H. M., Nicholls, C. W., Contamination Flashover Performance of Insulators for UHV, IEEE Trans. Power Appar. Syste., PAS-97 (1978), 1411-1420
  • [8] Zhijin, Z., Xinliang, J., Caixin, S., Jianlin, H., Haizhou, H., Study of the influence of test methods on DC pollution flashover voltage of insulator strings and its flashover process, IEEE Trans. Diele. Elect. Insul., 17 (2010), 1787-1795
  • [9] Xingliang, J., Jihe, Y., Zhijin, Z., Jianlin, H., Caixin, S., Study on AC Artificial-Contaminated Flashover Performance of Various Types of Insulators, IEEE Trans. Power Deliv., 22 (2007), 2567-2574
  • [10] Amendment to IEEE Standard Techniques for High-Voltage Testing, IEEE Std 4a-2001, 2001
  • [11] Artificial pollution tests on high-voltage insulators to be used on a.c. systems, IEC Std. 507, 1991
  • [12] Jiang, X., Chen, L., Zhang, Z., Sun, C., Shu, L., Effect of arclevitating from polluted insulators' surface in the low air pressure on its DC flashover performance, IET Gener. Transm. Distri., 5 (2011), 729-734