PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Impact of an extended grounding system on the factors affecting selection of an SPD system for apparatus safety

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Wpływ systemu uziemienia na efektywność ochrony urządzeń, narażonych na oddziaływanie przepięć
Języki publikacji
EN
Abstrakty
EN
The influence of an extended grounding system on the dimensioning of an SPD system for apparatus protection against lightning surges is investigated. In an extended earthing arrangement, an apparatus distant from the main switch board is usually protected by an SPD system consisting of a first SPD at the main switch board (SPD1) and of a downstream SPD close the apparatus (SPD2); if the SPD2 is earthed locally, additional stresses on such SPD are expected due to lack of equipotentiality of the extended earthing arrangement. In this paper the current and the associated charge expected at installation point of SPD2 have been investigated by several computer simulations performed by means of the transient software EMTP-RV.
PL
W artykule rozważany jest wpływ systemu uziemienia na efektywność ochrony urządzeń, narażonych na oddziaływanie przepięć. Analizowany jest przypadek uziemienia kratowego i urządzenia oddalonego od głównej tablicy rozdzielczej, które zazwyczaj jest chronione przez system SPD składający się z: SPD w głównej tablicy rozdzielczej (SPD1) oraz SPD przy urządzeniu chronionym (SPD2). W sytuacji gdzie SPD2 jest uziemione lokalnie, występuje dodatkowe zagrożenie w związku z brakiem ekwipotencjalizacji układu uziemiającego. Przedstawione badania dotyczą spodziewanych wartości prądu i ładunku w punkcie instalacji SPD2, które zostały wykonane za pośrednictwem symulacji komputerowych przy użyciu programu EMTP-RV.
Rocznik
Strony
51--53
Opis fizyczny
Bibliogr. 14 poz., rys., wykr.
Twórcy
  • Warsaw University of Technology, ul. Koszykowa 75, 00-662 Warsaw, Poland
autor
  • University of Rome “La Sapienza”, Via Eudossiana 18, 00-184 Rome, Italy
autor
  • University of Rome “La Sapienza”, Via Eudossiana 18, 00-184 Rome, Italy
autor
  • INAIL - Istituto Nazionale per l'Assicurazione contro gli Infortuni sul Lavoro, Dipartimento Innovazioni Tecnologiche e Sicurezza degli Impianti Prodotti e Insediamenti Antropici, Laboratorio di elettronica ed elettrotecnica, Via di Fontana Candida 1, 00-040 Monte Porzio Catone RM, Italy
Bibliografia
  • [1] IEC 62305-1, Ed. 2,0 2010-12, Protection against lightning – Part 1: General principles
  • [2] IEC 62305-3, Ed. 2,0 2010-12, Protection against lightning – Part 3: Physical damages and life hazard
  • [3] Ziemba R., Maslowski G., Karnas G., Wyderka S., Distribution of lightning current in the grounding grid for different multilayer soil models, 2012 ICHVE 2012 - 2012 International Conference on High Voltage Engineering and Application
  • [4] Parise, G., Martirano, L., Parise, L., Interferences between grounding systems in urban and industrial areas, IEEE IAS Electrical Safety Workshop 2015
  • [5] Grcev L., Heimbach M., Frequency dependent and transient characteristics of substation grounding systems, IEEE Transactions on Power Delivery, vol.12, n. 1, pp. 172-178, January 1997
  • [6] Pack S., Powersys: Use of the EMTP-RV software for insulation coordination studies, Graz, Austria, 18–20 October 2010
  • [7] Grcev L., Modeling of Grounding Electrodes Under Lightning Currents , IEEE Transactions on Electromagnetic Compatibility, Volume: 51 , Issue: 3 , Part: 1, 2009
  • [8] Lo Piparo G.B., Riccio T., Alcune osservazioni sul dimensionamento del dispersore negli impianti di protezione contr le scariche atmosferiche, L’Elettrotecnica, Ottobre 1969
  • [9] Grcev L., Heimbach M., Simulation of grounding structures within EMTP, Proceedings of 10th International Symposium on High Voltage Engineering, Montreal, Canada, August 1997
  • [10] Gatta F.M., Geri A., Lauria S., Maccioni, M., Generalized picircuit tower grounding model for direct lightning response simulation, Electric Power Systems Research, Vol. 116, 2014
  • [11] Kisielewicz T., Selected problems for the protection of electrical and electronic systems against lightning overvoltages, PhD thesis, Faculty of Civil and Industrial Engineering, Astronautic, Electrical and Energetic Engineering Department, ING-IND/33 – Electrical Systems for Energy, Sapienza University of Rome, Italy, 2013
  • [12] Grcev L., Impulse Efficiency of Ground Electrodes, IEEE Transactions on Power Delivery, Volume: 24 , Issue: 1, 2009
  • [13] Kisielewicz T., Fiamingo F., Flisowski Z., Kuca B., Lo Piparo G.B., Mazzetti C., Factors Influencing the Selection and Installation of Surge Protective Devices for Low Voltage Systems, International Conference on Lightning Protection 2012, Vienna, Austria, (IEEE Xplore)
  • [14] Kisielewicz T., Mazzetti C., Lo Piparo G.B., Kuca B., Flisowski Z., Electronic Apparatus Protection Against LEMP: Surge Threat for the SPD Selection, International Symposium on Electromagnetic Compatibility 2012, Rome, Italy, (IEEE Xplore)