Frequency dielectric response of aramid enhanced cellulose paper in aspect of Its water content determination

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Odpowiedź dielektryczna częstotliwościowa materiału celulozowego wzmocnionego aramidem w aspekcie wyznaczania jego zawilgocenia
Języki publikacji
EN
Abstrakty
EN
This article compares the dielectric response in the frequency domain of the aramid enhanced cellulose paper and cellulose paper. Based on results of the measurements, the characteristic of tanδ, measured at 10-3 Hz, in function of moisture content of the samples was created. The physical basis of this relationship has been explained. Using this characteristic, it is possible to determine the moisture content of aramid enhanced cellulose papers of different thickness, i.e. with possibly different percentage of cellulose and aramid, without the need for moisture patterns.
PL
W artykule przedstawiono porównanie odpowiedzi dielektrycznej w dziedzinie częstotliwości papieru celulozowego wzmocnionego aramidem znanego pod nazwą Nomex 910 oraz papieru celulozowego. Na podstawie charakterystyk tgδ w zależności od częstotliwości stworzono charakterystykę tgδ przy 10-3 Hz w zależności od zawilgocenia próbek. Wyjaśniono fizyczne podstawy tej zależności. Wykorzystując tę charakterystykę można wyznaczyć zawilgocenie materiałów celulozowych wzmocnionych aramidem o różnej grubości, tzn. o różnej procentowej zawartości celulozy i aramidu bez konieczności posiadania wzorców zawilgocenia.
Rocznik
Strony
23--26
Opis fizyczny
Bibliogr. 13 poz., rys.
Twórcy
  • Politechnika Poznańska, Instytut Elektroenergetyki, ul. Piotrowo 3a, 60-965 Poznań
  • Politechnika Poznańska, Instytut Elektroenergetyki, ul. Piotrowo 3a, 60-965 Poznań
  • Politechnika Poznańska, Instytut Elektroenergetyki, ul. Piotrowo 3a, 60-965 Poznań
  • Politechnika Poznańska, Instytut Elektroenergetyki, ul. Piotrowo 3a, 60-965 Poznań
  • DuPont, ul. Postępu 17B, 02-676 Warszawa
Bibliografia
  • [1] Szewczyk R., Marek R.P., Ballard R.C., Duart J.C., Vercesi, G. Innovative insulation materials helping in cost reduction of modern transformers, proceedings of the 25th International Conference on Electricity Distribution CIRED, Madrid, 3-6 June 2019, Paper No 2108
  • [2] Szewczyk R., Duart J.C., Trifigny P., Mitigation of lock-in effect for compact substations with transformers meeting future EU efficiency regulations, proceedings of the 25th International Conference on Electricity Distribution CIRED, Madrid, 3-6 June 2019, Paper No 2089
  • [3] Johnson Marek R.P., Calil W., Galhardo L., Souza A., Practical verification of a high temperature insulation system for power transformers, proceedings of the IX WORKSPOT - International Workshop on Power Transformers, Equipment, Substations and Materials, Brasil, 25-28 November 2018
  • [4] Oommen T.V., Lindgren S.R, Bubble evolution from transformer overload, proceedings of the Transmission and Distribution Conf. Exposition, IEEE/PES, 1 (2001), pp. 137-142
  • [5] Sakai M., Maki K., Taniguchi Y., Daikuhara N. and Yanabu S., A Research of Critical Temperature on Bubble Formation under Overloaded Oil-Immersed Transformer, Trans. Inst. Electr. Eng. Japan, 121-B (2001), 500-506
  • [6] Lu Y., Chao N., Zhao T. Tong Y., Jia C., Mechanism and numerical model of bubble effect in oil-paper insulation based on microtubule model, IEEE Trans. Dielectr. Electr. Insul. (27) 2020, n. 5, 1529-1537
  • [7] Prosiński S., Chemia drewna, PWRiL, Warsaw, Poland, 1984
  • [8] Gielniak J., Graczkowski A., Moranda H., Przybylek P., Walczak K., Nadolny Z., Moscicka-Grzesiak H., Gubanski S.M., Feser K., Moisture in cellulose insulation of power transformers: statistics, IEEE Trans. Dielectr. Electr. Insul. (20) 2013, n. 3, 982-987
  • [9] Przybylek P., A comparison of bubble evolution temperature in aramid and cellulose paper, proceedings of the IEEE International Conference on Solid Dielectrics, Bologna, Italy, June 30 – July 4, 2013
  • [10] Gubanski S.M., Boss P., Csepes G., Houhanessian V.D., Filippini J., Guuinic P., Gafvert U., Karius V., Lapworth J., Urbani G., Werelius P., Zaengl W.S., Dielectric response methods for diagnostics of power transformers. Report of the TF D1.01.09. Brochure of CIGRE No 254, 2002
  • [11] Gubanski S.M., Blennow J., Holmgren B., Koch M., Kuechler A., Kutzner R., Lapworth J., Linhjell D., Tenbohlen S., Werelius P., Dielectric response diagnoses for transformer windings, Brochure of CIGRE No 414, 2010
  • [12] Gubanski, S.M., Blennow J., Karlson L., Feser K., Tenbolen S., Neumann C., Moscicka-Grzesiak H., Filipowski A., Tatarski L., Reliable Diagnostics of HV Transformer Insulation for Safety Assurance of Power Transmission System. REDIATOOL - European Research Project, CIGRE General Session D1–207, 2006, pp. 15
  • [13] Young D.M., Crowell A.D., Physical Adsorption of Gases, Butterworth & Co Limited, London, England, 1962
Uwagi
Opracowanie rekordu ze środków MNiSW, umowa Nr 461252 w ramach programu "Społeczna odpowiedzialność nauki" - moduł: Popularyzacja nauki i promocja sportu (2021).
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-9366e200-4ef2-4c97-96e9-5c3388a7ef06
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.