PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Vibration isolation of variable fan speed in HVAC systems

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Wibroizolacja wentylatorów ze zmienną prędkością obrotową w systemach HVAC
Języki publikacji
EN
Abstrakty
EN
This article analyses two samples of existing vibration isolation systems. The first sample applies to rubber absorbers, the second, to spring absorbers. The article presents a method of setting the parameters of a second order differential equation describing oscillation movement. The equation parameters were selected on the basis of amplitude measurement and rotation velocity in two representative points – (i) in the resonance and (ii) at the maximum rotation velocity when the influence of the damping factor for the oscillation amplitude can be ignored. Equations of motion simulations were performed and the results were compared with the actual values of displacement and the velocity vibration platform.
PL
W artykule przeanalizowano pracę dwóch rzeczywistych układów wibroizolacji. Pierwszy przypadek dotyczył wibroizolatorów gumowych, drugi przypadek amortyzatorów sprężynowych. Przedstawiono metodę wyznaczania parametrów równania różniczkowego drugiego rzędu opisującego ruch drgający. Parametry równania zostały wyznaczone na podstawie pomiaru amplitudy i prędkości obrotowej w dwóch charakterystycznych punktach: (i) w rezonansie oraz (ii) przy maksymalnej prędkości obrotowej, kiedy wpływ współczynnika tłumienia na amplitudy drgań może zostać pominięty. Przeprowadzono symulacje równania ruchu, a wyniki porównano z rzeczywistymi wartościami przemieszczeń i prędkości platformy wibracyjnej.
Rocznik
Strony
31--44
Opis fizyczny
Bibliogr. 10 poz., wz., wykr., tab.
Twórcy
  • Department of Heating and Air Conditioning, Faculty of Environmental Engineering, Wrocław University of Technology
  • Department of Heating and Air Conditioning, Faculty of Environmental Engineering, Wrocław University of Technology
  • Department of Heating and Air Conditioning, Faculty of Environmental Engineering, Wrocław University of Technology
Bibliografia
  • [1] Ibrahim R.A., Recent advances in nonlinear passive vibration isolators, Journal of Sound and Vibration 314, 2008, 371-452.
  • [2] Yang C., Yuan X., Wu J., Yang B., The research of passive vibration isolation system with broad frequency field, Journal of Vibration and Control 19(9), 2012, 1348-1356.
  • [3] Le T.D., Ahn K.K., Experimental investigation of a vibration isolation system using negative stiffness structure, International Journal of Mechanical Sciences 70, 2013, 99-112.
  • [4] Liu X., Huang X., Hua H., On the characteristics of a quasi-zero stiffness isolator using Euler buckled beam as negative stiffness corrector, Journal of Sound and Vibration 332, 2013, 3359-3376.
  • [5] Hanieh A.A., Preumont A., Multi-axis vibration isolation using different active techniques of frequency reduction, Journal of Vibration and Control 17(5), 2010, 759-768.
  • [6] Alujević N., Wolf H., Gardenio P., Tomac I., Stability and performance limits for active vibration isolation using blended velocity feedback, Journal of Sound and Vibration 330, 2011, 4981-4997.
  • [7] Michalczyk J., Transient resonance of machines and devices in general motion, Journal of Theoretical and Applied Mechanics, 50, 2, Warsaw 2012, 577-587.
  • [8] DiGiovanni M., Thomas R., Spearman P.E., Fan Vibration Specifications, ASHRAE Journal, February 2008.
  • [9] Goliński J.A., Wibroizolacja maszyn i urządzeń, WNT, Warszawa 1979.
  • [10] ISO 10816-1 Annex B, Mechanical vibration – Evaluation of machine vibration by measurements on non-rotating parts, 2003.
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-86197934-9b5f-487a-a633-830c7754869e
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.