Evaluation of short-circuit currents in power network design process

Autorzy
Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Obliczanie prądów zwarciowych w procesie projektowania sieci elektroenergetycznych
Języki publikacji
EN
Abstrakty
EN
The paper presents some aspects of short-circuit current calculations in power system design, including: • standardisation of short-circuit current calculations and factors; • short-circuit current computation; • short-circuit current calculation in the networks with solidly earthed neutral; • short-circuit current calculation in the networks with not solidly earthed neutral; • short-circuit calculations for the purposes of power system protection.
PL
W pracy omówiono różne problemy obliczanie prądów zwarciowych w procesie projektowania sieci elektroenergetycznych, w tym: zagadnienia normowanie obliczeń prądów i wskaźników zwarciowych, metody stosowane w komputerowych obliczeniach zwarciowych, obliczanie prądu zwarciowego podczas zwarć wielkoprądowych czy podczas zwarć doziemnych w sieci z nieskutecznie uziemionym punktem neutralnym, obliczenia zwarciowe dla potrzeb elektroenergetycznej automatyki zabezpieczeniowej.
Rocznik
Tom
Strony
23--39
Opis fizyczny
Bibliogr. 83 poz.
Twórcy
autor
  • Institute of Electrical Power Engineering, Technical University of Lodz
Bibliografia
  • [1] A. Wiszniewski: Co projektant zabezpieczeń powinien wiedzieć o prądach zwarciowych. Ref. nr 1.1./I-1983.
  • [2] Z. Kowalski: Ogólne problemy praktycznych obliczeń prądów zwarciowych w układach elektroenergetycznych. Ref. nr 1.2/I-1983.
  • [3] P. Kacejko: Obliczanie warunków zwarciowych w dużych systemach elektroenergetycznych w aspekcie wzrostu liczby sprzężonych ze sobą linii napowietrznych. Ref. nr 2.5/I-1983.
  • [4] A. Kanicki: Obliczanie wskaźnika cieplnego prądu zwarciowego. Ref. nr 2.6/I-1983.
  • [5] G. Bartodziej: Wyznaczanie udziału silników asynchronicznych w prądach zwarciowych. Ref. nr 3.5./I-1983.
  • [6] W. Przanowski: Algorytm wyznaczania prądów zwarcia trójfazowego w sieci z duża liczbą silników asynchronicznych. Ref. nr 3.6./I-1983.
  • [7] A. Kanicki: Analiza możliwości i celowości uwzględniania obciążenia generatorów przed zwarciem w praktycznych obliczaniach zwarciowych. Ref. nr 3.7/I-1983.
  • [8] H. Belka: Prądy zwarcia doziemnego w kablowych izolowanych sieciach średniego napięcia zawierających linie wielotorowe. Ref. nr 1.1./II-1985.
  • [9] J. Bujalski, S. Melcer: Automatyzacja obliczeń wielkości zwarciowych i nastawień zabezpieczeń linii 110, 220,400 kV dla potrzeb ZEO. Doświadczenia eksploatacyjne. Ref. nr 1.3./II-1985.
  • [10] E. Hibner, J. S. Zieliński: Wybrane zagadnienia z analizy wielokrotnych asymetrii. Ref. nr 1.5./II-1985.
  • [11] P. Kacejko: Ocena zależności parametrów linii napowietrznych od wartości rezystancji uziemień slupów z uwzględnieniem ich losowego charakteru. Ref. nr 1.6./II-1985.
  • [12] P. Kacejko, R. Zych: Automatyzacja obliczeń wielkości zwarciowych i nastawień zabezpieczeń linii 110, 220 i 400 kV dla potrzeb ZEO - uwagi o metodach numerycznych i organizacji procesu przetwarzania. Ref. nr 1.7./II-1985.
  • [13] S. Kobosko, Z. Łagowski: Czasy trwania zwarć w liniach 750, 400, 220 i 110 kV.. Ref. nr 1.8./II-1985.
  • [14] S. Kobosko, Z. Łagowski: Zastępcze stałe czasowe składowej nieokresowej prądu zwarciowego. Ref. nr 1.9/II-1985.
  • [15] T. Bułat, J. Pytel: Metody obliczania prądów zwarciowych w przemysłowych sieciach elektroenergetycznych. Ref. nr 3.17/II-1985.
  • [16] G. Bartodziej, M. Szadkowski: Założenia do nowelizacji normy PN-74/E-05002. Ref. nr 1.1/III-1988.
  • [17] А. П. Берман, А. И. Фраткин: Расчет несимметричных режимов електрических систем методом компаунд сетей. Ref. nr 1.2./III-1988.
  • [18] A. Bogucki, Р. Sowa: Zastosowanie symulacyjnego programu mikrokomputerowego do obliczania rozpływu prądów zwarciowych w układzie elektroenergetycznym. Ref. nr 1.3/III-1988.
  • [19] J. Bujalski, R. Zych: Obliczanie nastawień zabezpieczeń linii najwyższych napięć na EMC Odra 1305 wspomagane stanowiskiem mikrokomputerowym. Ref. nr 1.5/III-1988.
  • [20] M. Hajro, M. Kusljugic: Calculating short-circuit currents in industrial power system. Ref. nr 1.11./III-1988.
  • [21] P. Kacejko: Redukcja modeli sieci do obliczeń zwarciowych poprzez agregację węzłów. Ref. nr 1.12/III-1988.
  • [22] A. Kanicki: Obliczanie zakłóceń wielokrotnych za pomocą maszyny cyfrowej. Ref. nr 1.13/III-1988.
  • [23] M. V. Kiorsak, V.M. Postolaty, S. H. Feigis: Computation of short-circuit asymmetric currents in the electric power systems with polyphase power transmission lines. Ref. nr 1.14/III-1988.
  • [24] S. Kobosko, A. Magdziarz, Z. Żagań: Prądy i napięcia w fazach nieuszkodzonych podczas zwarć w linii obciążonej symetrycznie. Ref. nr 1.16/III-1988.
  • [25] В. Г. Кузнецов Ю. И. Тугай: Подсистема анализа аварийных режимов распределительных електрических сетей. Ref. nr 1.17./III-1988.
  • [26] J. Niebrzydowski, W. Cyganków: Interakcyjna metoda obliczania zwarć w elektroenergetycznych sieciach rozdzielczych z wykorzystaniem mikrokomputera. Ref. nr 1.21./III-1988.
  • [27] G. Parise: The "Charasteristic" curerents method for the short-circuit analysis in power system networks. Ref. nr 1.22./III-1988.
  • [28] J. Pytel, T. Bulat: Obliczanie prądów zwarciowych z uwzględnieniem zanikania składowej okresowej. Ref. nr 1.25./III-1988.
  • [29] Z. Zdun: Modele trójfazowe elementów SEE w obliczeniach zwarciowych. Ref. nr 1.31 ./III-1988.
  • [30] J. Skierski: Moce i prądy zwarciowe w potrzebach własnych bloków energetycznych dużej mocy. Ref. nr 2.7/III-1988.
  • [31] В. В. Жуков: Особенности учета нагрузки при расчете токов короткого замыкания. Ref. nr 2.8./III-1988.
  • [32] N. М. Assi, K.L. Lo, M.I. Khan: New matrix approach for fault analysis in large power systems. Ref. nr 1.1./IV-1990.
  • [33] N. M. Assi, K.L. Lo: Computer-aided analysis of some problems of network modification and fault analysis. Ref. nr 1.2./IV-1990.
  • [34] G.P. Granelli, S. Massucco, M. Montagna, G. L. Pasini, F. Tommazzoli: Calculation of short-circuit currents comparison of the IEC 909 standard procedure with a dynamic simulation program. Ref. nr 1.6./IV-1990.
  • [35] D. Oeding: Calculation of short-circuit currents, IEC-Publ. 909 (1988), factors. Ref. nr 2.1./IV-1990.
  • [36] A. Kanicki: Calculation of Short-circuit Quantities in Networks with Asynchronous Motors. Ref. nr 2.5./IV-1990.
  • [37] V. Tchemyakov: The PC program for short-circuit current calculation in the network containing up to 3000 nodes. Ref. nr 4.12./IV-1990.
  • [38] A. Kanicki: Reduction of on Electric Power System Model. Ref. nr 1.17./TV-1992.
  • [39] M.A. Al-Tai, M. R. Withers: Digital computation of fault levels in power systems. Ref. nr 1.23./IV-1992.
  • [40] E. Anderson, J.Karolak, Z. Piątek: Calculation of single- and double-fault currents in M.V. underground-cable networks. Ref. nr 1.24./IV-1992.
  • [41] A. Berizzi, F. Castelli Dezza, S. Massucco, A. Silvestri, D. Zaninelli: Evolution of international standards for short-circuit current calculation: A comparative analysis supported by simulation tests. Ref. nr 1.31./IV-1992.
  • [42] U. Grasselli, G. Parise: Short-circuit currents evaluation on emergency power systems. Ref. nr 1.32./IV-1992.
  • [43] A. Augugliaro, A. Campoccia, V. Cataliotti, L. Dusonchet, G. Morana: Analysis of simultaneous short-circuit in MV radial distribution networks. Ref. nr 1.33./IV-1992.
  • [44] A. Berizzi, S. Massucco, A. Silvestri, D. Zaninelli: ANSI/IEEE and IEC standards for short-circuit current evaluation: methodologies, computed values and results. Ref. nr l.l/VI-1994.
  • [45] G. Parise: Far-from-generator and near-to-generator short-circuit analysis: the "characteristic" currents method. Ref. nr 1.2./VI-1994.
  • [46] A. Kanicki: Algorithm for multiple fault computations. Ref. nr 1.6./VI-1994.
  • [47] Th. Hunger, D. Oeding: Short-circuit currents between generator and unit transformer. Ref. nr 1.19./VI-1994.
  • [48] D. Oeding, Th. Huneger: Partial short-circuit currents of power station units at the high voltage side of the unit transformer with and without on-load tap changer. Ref. nr 1.20./VI-1994.
  • [49] V. Boschnega: Calculation of steady-state short-circuit currents in electric networks with transformer. Ref. nr 1.24./VI-1994.
  • [50] J. Dobrogowski: Earth fault factor determination. Ref. nr 1.27./VI-1994.
  • [51] T. Bełdowski, E. Tomaszewicz, Z. Zdun: The software package for short-circuit analysis in electric power network of heating power stations. Ref. nr 1.41./VI-1994.
  • [52] J. Kozłowski, J. Wiśniewski: Choice of the best value of line to ground short- circuit current in MV network with resistor in neutral point. Ref. nr 3.4./VI-1994.
  • [53] J. Andruszkiewicz, A. Trzeciak: Decision support system of fault current calculations for determination of overcurrent protection settings in distribution lines. Ref. nr 3.7./VI-1994.
  • [54] S. Otto, D. Oeding: Partial short-circuit currents to determine the suitable operating characteristic of distance-protection relays for double-circuit lines. Ref. nr 3.8./VI-1994.
  • [55] U. Grasseli, G. Parise: Short-circuit currents as designing parameters of building power systems. Ref. nr 3.14./VI-1994.
  • [56] M. Dołowy, S. Kobosko: The coefficient of earth-fault compensation during faults in high voltage lines. Ref. nr 3.17./VI-1994.
  • [57] N. M. Assi: Algorytm dokładniejszych obliczeń zwarciowych sieci elektroenergetycznych. Przegląd Elektrotechniczny 1991, nr 9.
  • [58] P. Kacejko: Uwagi o praktycznych obliczeniach zwarciowych. Przegląd Elektrotechniczny 1992, nr 7.
  • [59] K. Zollenkopf: Sparse nodal impedance matrix generated by the bi-factorisation method and applied to short-circuit studies. PSCC, Cambridge 1975 r.
  • [60] W. F. Tinney, V. Brandwajn, S. M. Chan: Sparse vector methods. IEEE Trans. PAS, vol. 104, 1985, nr 2.
  • [61] G. W. Stagg, A. H. El-Abiad: Computer Methods in Power System Analysis. Me Graw-Hill, New York, 1968.
  • [62] M. A. Laughton: Analysis of unbalanced phase networks by the method of phase coordinates. Proceedings IEE, part 1 vol. 115, pp. 1163-1172; part 2 vol. 116, pp. 857-869.
  • [63] Z. Dagher: Phase coordinate modelling and analysing of power system networks. Ph. D. Thesis, Technical University of Warsaw, 1989.
  • [64] P. Kacejko: Obliczanie złożonych zakłóceń w sieciach systemu elektroenergetycznego. Prace Naukowe Politechniki Lubelskiej, Elektryka, nr 25,1990 r., str.51-80.
  • [65] P. Kacejko, P. Miller: IEC 909 Standard is it all power engineers need? Ref. nr 1.1./VII-1996.
  • [66] A. Conejo, J. M. Arroyo: Two-line faults. Ref. nr 1.2./VII-1996.
  • [67] D. Sweeting: The Joule integral of short circuit currents. Ref. nr 1.3./VII-1996.
  • [68] W. Mielczarski, G. Michalik: Australian Standards for short-circuit currents calculation description and comparison with the IEC and ANSI Standards. Ref. nr 1.4./VII-1996.
  • [69] T. Hunger, D. Oeding, G. Seifen: Line-to-earth short-circuit currents at high- voltage side of unit transformers. Ref. nr 1.7./VII-1996.
  • [70] D. Oeding, T. Hunger, G. Waider: Impedance correction factor for network trnsformers when calculating short-circuit currents according to IEC 909. Ref. nr 1.8./VII-1996.
  • [71] A. Kanicki, T. Piotrowski: Calculation of thermal equivalent short-circuit current. Ref. nr 1.10./VII-1996.
  • [72] A. Berizzi, A. Silvestri, D. Zaninelli, S. Massucc., F. Tommazzolli: Short-circuit current calculation for eletrical system design: general methodologies and International Standards. Ref. nr 1.13./VII-1996.
  • [73] S. Otto, K. J. Junglas: The influence of partial short-circuit currents on overhead lines in meshed HV-systems on the distance protection performance. Ref. nr 1.16./VII-1996.
  • [74] A. Torres, G. J. Anders: Sispot-new windows-based computer software for short circuit, transient, stability and load flow calculations on a deskop computer. Ref. nr 1.30./VII-1996.
  • [75] F. Sato, A. Alves, A. V. Garcia: A comparative study of parallel and distributed probabilistic short-circuit analysis. Ref. nr 1.31./VII-1996.
  • [76] К. M. Zhou, D. C. Macdonald, I. P. Forbes: Development of time-dependent model for asymmetrical short-circuit curmt computation. Ref. nr 1.34./VII-1996.
  • [77] H. A. Niederheitmann: Graphic user interface for short-circuit simulation. Ref. nr 1.35./VII-1996.
  • [78] J. C. Das: Short-circuit calculations - ANSI/IEEE and IEC methods, similarities and differences. Ref. nr 1.3./VIII-1998.
  • [79] C. J. van de Water: Fault analysis with sequential network modifications. Ref. nr 1.4./VIII-1998.
  • [80] R. Hrubji, Z. Zdun: Short-circuit current flow to the equivalent large scale power transmission network. Ref. nr 1.7./VIII-1998.
  • [81] R. Aresi, S. Massucco, M. P. Bottino, G. Rebaudengo: Considerations on short- circuit currents and related problems an AC Medium Voltage electrical networks aboard ships and offshore units. Ref. nr 1.9./VIII-1998.
  • [82] C. Saldana, G. Calzolari: Short-circuit currents calculation at substation “Montevideo E”. Ref. nr 1.15./VIII-1998.
  • [83] D. Oeding: Current through earth and earth potentials in case of line-to-earth short circuit at towers of high-voltage lines outside a transformer station. Ref. nr4.48./VIII-1998.
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-84506753-4878-47da-b610-d64c216f4381
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.