PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Nonlinear phenomena in tank of transformer and power losses computations

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Analiza zjawisk nieliniowych oraz strat w kadzi transformatora
Języki publikacji
EN
Abstrakty
EN
The paper presents the design methodology of magnetic screens based on the three-dimensional field calculations. In this paper a new approach on the designing of the magnetic screens covers located on the tank is presented, so as to determine the optimal geometry (i.e. their thickness), that minimizes the aggregate losses not only in the tank but also in the configuration screen - tank. The transformer model was developed using the field-circuit oriented excitation. The load corresponds to the actual transformer's grid connected operating conditions. The electromagnetic field analysis leads to the identification of high loss density points in the structure.
PL
W pracy przedstawiono metodologię projektowania ekranów magnetycznych na podstawie trójwymiarowych obliczeń polowych. Zaprezentowano nowe podejście w projektowaniu ekranów magnetycznych umieszczonych na ściankach kadzi w celu ustalenia jej optymalnej geometrii (grubości), w celu minimalizacji łącznych strat nie tylko w kadzi, ale również w konfiguracji ekran - kadź. Model transformatora został opracowany jako polowo-obwodowy. Przyjęto znamionowe obciążenie transformatora. Przeprowadzona analiza pola elektromagnetycznego ma na celu identyfikację obszarów o wysokiej gęstości strat w badanym obiekcie.
Rocznik
Strony
230--232
Opis fizyczny
Bibliogr. 18 poz., rys.
Twórcy
autor
  • Lodz University of Technology
autor
  • Lodz University of Technology
autor
  • Lodz University of Technology
Bibliografia
  • [1] Wiak S., Drzymała P., Welfle H. (2007) "Computer model of 3D shunt reactor structure in optimisation strategy", 8th Conference on Diagnostic of Processes and Systems, DPS’2007, 10-12 September 2007, Słubice – Poland
  • [2] Drzymała P., Welfle H.: Trójwymiarowa analiza pola i sił działających na uzwojenia transformatora blokowego. Przegląd Elektrotechniczny (Electrical Review), 2010, rocznik LXXXVI, nr 12, s. 263-266
  • [3] Drzymala P., Welfle H.: Numeryczne metody modelowania uzwojeń transformatorów dużych mocy. Przegląd Elektrotechniczny (Electrical Review), 2011, R. 87 NR 2/2011, s.191-194.
  • [4] Drzymala P., Welfle H., Wiak S.: Modeling of 3D electromagnetic field distributions of a large power transformer, Przegląd Elektrotechniczny (Electrical Review), R. 86 NR 8/2010 page 131-134.
  • [5] Wosiak A., Lipiński P., Kaźmierski M., Kersz I.:Optymalizacja układu chłodzenia w systemie nadzorującym pracę transformatorów sieciowych: Przegląd elektrotechniczny (Electrical Review), ISSN 0033-2097, R. 85 NR 12/2009, s.166-169
  • [6] Drzymala P., Welfle H.: Field methods for calculating the magnetic screen of large power transformers. Przegląd Elektrotechniczny (Electrical Review), ISSN 0033-2097, R. 88 NR 4a/2012, s. 77-81. (Metody polowe w obliczaniu ekranów magnetycznych transformatorów dużych mocy)
  • [7] Drzymala P., Welfle H.: Analysis of electromagnetic phenomena and losses in the power transformer clampingrods. Przegląd Elektrotechniczny (Electrical Review), ISSN 0033-2097, R. 88 NR 4a/2012, s.82-85. (Analiza zjawisk elektromagnetycznych i strat w konstrukcji łączników belek transformatorów dużych mocy)
  • [8] Kralj L., Miljavec D. (2010), "Stray losses in power transformer tank walls and construction parts", XIX International Conference on Electrical Machines - ICEM 2010, 6-8 Sept. 2010 Rome
  • [9] Motalleb M., Vakilian M., Abbaspour A. (2009) "Tank shielding contribution on reduction of eddy current losses in power transformers," Pulsed Power Conference, PPC '09. IEEE , pp. 641–645, 2009.
  • [10] Susnjic L., Haznadar Z., Valkovic Z. (2008), "3D finite-element determination of stray losses in power transformer", Electric Power Systems Research 78, pp. 1814–1818, 2008.
  • [11] Ho S.L., Li Y., Tang R.Y., Cheng K.W.E., Yang S.Y. (2008), "Calculation of Eddy Current Field in the Ascending Flange for the Bushings and Tank Wall of a Large Power Transformer" IEEE Trans. on Magn., vol. 44, no. 6, pp. 1522 -1525, June 2008.
  • [12] Villar I., Viscarret U., Etxeberria-Otadui I., Rufer A. (2009) “Loss Evaluation Methods for Nonsinusoidally Fed Medium-Frequency Power Transformers” IEEE Trans. Ind. Electron., vol.56, no. 10, oct. 2009
  • [13] Takahashi N., Kitamura T., Horii M., Takehara J. (2000) “Optimal design of tank shield model of transformer” IEEE Trans. Magn., vol. 36, no. 4, pp. 1089– 1093, Jul. 2000.
  • [14] Schmidt E., Hamberger P., Seitlinger W. (2003), “Finite Element Calculation of Eddy Current Losses in the Tank Wall of Power Transformers” Electric Machines and Drives Conference, IEMDC'03. IEEE International, vol. 2, pp. 1167–1173, 2003.
  • [15] Venegas Vega M.A., Escarela Pérez R., Niewierowicz T. (2008), "3D Finite Element Estimation of Stray Losses in Three-Phase Transformers," Journal of Applied Computer Science, Vol. 16. No 1 pp.89-100, 2008.
  • [16] Wiak S., Drzymała P., Welfle H. (2004), "Virtual Modelling and Optimal Design of Intelligent Micro-Accelerometers", International Conference on Artificial Inteligence and Soft Computing, Zakopane 2004, Poland
  • [17] Turowski J. et al. (1997) “Eddy current losses and hot-spot evaluation in cover plates of power transformer,” Proc. Inst. Elect. Eng.—Electr. Power Appl., vol. 144, no. 6, pp. 435–440, Nov. 1997
  • [18] Majer K.:The analysis of the vibrations of the cores of model transformers. Przegląd Elektrotechniczny (Electrical Review) 4/2010, s. 174-178.
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-82e1d06c-27fc-451e-a3cf-88ecb9765e54
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.