System utrzymywania stałej temperatury w powietrznej komorze termostatycznej
Języki publikacji
Abstrakty
In this paper, a system for maintaining constant temperature in an thermostatic air chamber is described. Temperature regulation in this chamber is based on a Peliter module and a PID temperature controller. This system is designed to stabilize the temperature of resistance standards during measurements, but may be used for other purposes. Results of long-term tests and the results of the environmental conditions influence on the temperature stabilization in the chamber indicate that the system is capable of stabilizing the temperature in the chamber within ±0.01 °C.
W artykule opisano system utrzymywania stałej temperatury w powietrznej komorze termostatycznej. Regulacja temperatury w komorze oparta jest na module Pelitera oraz regulatorze temperatury PID. Ten system przeznaczony jest do stabilizacji temperatury wzorców rezystancji podczas pomiarów, ale może być użytkowany dla innych celów. Wyniki długoterminowych badań oraz wyniki wpływu warunków środowiskowych na stabilizację temperatury w komorze wskazują, że system jest w stanie stabilizować temperaturę w komorze do ±0,01°C.
Wydawca
Czasopismo
Rocznik
Tom
Strony
44--47
Opis fizyczny
Bibliogr. 13 poz., rys., tab.
Twórcy
autor
- Wrocław University of Science and Technology, ul. Wyb. Wyspiańskiego 27, 50-370 Wrocław
autor
- Independent Researcher
autor
- Wrocław University of Science and Technology, ul. Wyb. Wyspiańskiego 27, 50-370 Wrocław
Bibliografia
- [1] Satish, et al., Determination and Comparison of Temperature Coefficient of Standard Inductors by Measuring Change in Inductance and Resistances. MAPAN 29, 73–76 (2014)
- [2] Boella G., Galliana F., Analysis of the voltage coefficient of high value standard resistors, Measurement, vol. 41, 1, 2008, p. 1-9
- [3] Turner L.B., Constant temperature: a study of principles inelectric thermostat design; and a mains-operated isothermal chamber constant to one-thousandth of a degree centigrade. Institution of Electrical Engineers - Proceedings of the Wireless Section of the Institution 1937, vol. 12, Issue 36
- [4] Fan K. C. et al., Development of a constant temperature environment chamber with high stability. Materials Science Forum, vol. 594, 2008, pp. 78-83
- [5] Jarrett D. G., Constant temperature and humidity chamber for standard resistors. Proc. of NCSL Workshop and Symposium, July 16-20, 1995, pp .501-505
- [6] Feng J. et al., Development of a low-cost and vibration-free constant-temperature chamber for precision measurement. Sensors and Materials, vol. 27, No. 4, 2015, pp. 329–340
- [7] Model 9300 temperature controlled air bath. Available online: www.mintl.com (Nov. 2, 2020)
- [8] 5030 series high precision variable temperature air bath. Available online: www.guildline.com (Nov. 2, 2020)
- [9] Krawczyk K., Kocjan B., Lisowski M., Double path system forresistance unit transfer from QHR primary standard to 100 TΩ standards. Proceedings of Conference on Precision Electromagnetic Measurements, Ottawa, Canada, 8-13 July 2016, pp. 1-2
- [10] Lisowski M., Krawczyk K., Resistance scaling from 10 kΩ up to 100TΩ with new designs of Hamon transfer devices. IEEE Transactions on Instrumentation and Measurement, vol. 62, no 6, pp. 1749-1754, 2013
- [11] Lisowski M., Krawczyk K., Method for ensuring constant airtemperature in the housing, for precision resistors, PL Patent 219697, Nov. 2, 2010
- [12] Lisowski M., Krawczyk K., Thermostatic chamber, especially for precision and reference resistors, PL Patent 219694, Nov. 2, 2010
- [13] Kocjan B., Krawczyk, K., Snopek L., Jasinski R., Dudek, E., Temperature chamber with precise temperature stability. Proceedings of Conference on Precision Electromagnetic Measurements, Paris, France, 8-13 July 2018