PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Method for determining the actual pressure value in a MV vacuum interrupter

Treść / Zawartość
Identyfikatory
Warianty tytułu
PL
Metodaokreślania rzeczywistej wartości ciśnienia w próżniowej komorze gaszeniowej SN
Języki publikacji
EN
Abstrakty
EN
The paper describes the author's method for determining the actual pressure value in a vacuum interrupter of a MV disconnector during high-voltage laboratory tests. The need to develop such a method was due to the lack of possibility to measure the pressure directly in the vacuum interrupter during the tests. There was a risk of damaging the vacuum gauge as a result of an electrical jump. The proposed method consists in measuring, in de-energized conditions, the difference in pressure between a set of vacuum pumps and a prototype vacuum interrupter made for the purpose of implementing this method. Thus, knowing the pressure value at the pumps and having the scaling characteristics of the system determined, it will be possible to determine the actual pressure inside the tested MV disconnecting extinguishing interrupter during high-voltage tests. Measurements of pressure drop in the pumping channel were carried out for air and three electro-negative gases: helium, argon and neon, used in the study by the authors of this paper.
PL
W artykule opisano autorski sposób pozwalający na określenie rzeczywistej wartości ciśnienia w próżniowej komorze rozłącznikowej SN podczas wysokonapięciowych badań laboratoryjnych. Konieczność opracowania metody tego typu wynikła z braku możliwości pomiaru ciśnienia bezpośrednio w komorze próżniowej w trakcie badań. Istniało bowiem ryzyko uszkodzenia próżniomierza w wyniku przeskoku elektrycznego. Proponowana metoda polega na pomiarze w warunkach beznapięciowych różnicy ciśnienia pomiędzy zestawem pomp próżniowych, a prototypem komory próżniowej wykonanym dla potrzeb realizacji tej metody. Dzięki temu znając wartość ciśnienia przy pompach oraz mając wyznaczone charakterystyki skalowania układu, w trakcie badań wysokonapięciowych możliwe będzie określenie rzeczywistego ciśnienia wewnątrz badanej rozłącznikowej komory gaszeniowej SN. Przeprowadzono pomiary spadku ciśnienia w kanale pompowym dla powietrza oraz trzech gazów elektroujemnych: helu, argonu oraz neonu, wykorzystywanych w badaniach przez autorów niniejszego artykułu.
Rocznik
Strony
28--31
Opis fizyczny
Bibliogr. 11 poz., tab., rys., wykr.
Twórcy
autor
  • Lublin University of Technology, Faculty of Electrical Engineering and Computer Science, Lublin, Poland
  • Lublin University of Technology, Faculty of Electrical Engineering and Computer Science, Lublin, Poland
Bibliografia
  • [1] Konarski M., Węgierek P.: The use of power restoration systems for automation of medium voltage distribution grid. Przegląd Elektrotechniczny 7/2018, 167–172.
  • [2] Kyoto Protocol to the UN Framework Convention on Climate Change. Kyoto 1997.
  • [3] Lech M.: Disassemblable vacuum interrupter as an innovative test stand designed for research on improving the operational parameters of power switching apparatus. Informatyka, Automatyka, Pomiary w Gospodarce i Ochronie Środowiska – IAPGOS 3/2020, 66–69.
  • [4] Leybold company data sheets.
  • [5] Ordinance of the Minister of Economy of 4 May 2007 on detailed conditions of the power system operations.
  • [6] Power engineering, distribution and transmission, Polish Power Transmission and Distribution Association’s Report, Poznań, 2020.
  • [7] Quality Regulation 2018 – 2025 for Distribution System Operators.
  • [8] Regulation (EU) No 517/2014 of the European Parliament and of the Council of 16 April 2014 on fluorinated greenhouse gases.
  • [9] Slade P. G.: The Vacuum Interrupter Theory, Design, and Application, CRC Press 2007.
  • [10] Węgierek P., Lech M.: Test stand for testing and diagnostics of medium voltage vacuum interrupters. Przegląd Elektrotechniczny 2/2021, 176–179.
  • [11] Węgierek P., Staszak S., Pastuszak J.: EKTOS – innovative medium voltage outdoor vacuum disconnector in a closed housing dedicated to the Network smart grids. Wiadomości Elektrotechniczne 11/2019, 21–25.
Uwagi
Opracowanie rekordu ze środków MNiSW, umowa Nr 461252 w ramach programu "Społeczna odpowiedzialność nauki" - moduł: Popularyzacja nauki i promocja sportu (2021).
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-7d16ce7a-c1e2-466d-9ae0-b39a44178a23
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.