PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Determination of the place and degree of damage insulation in cables

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Określenie miejsca i stopnia uszkodzenia izolacji w kablach
Języki publikacji
EN
Abstrakty
EN
A new method has been developed to determine the location and degree of insulation damage in cables. An electrical circuit is defined, using which this task is performed. According to this scheme, one end of the cable is connected to a pulsed voltage source through a small resistance, and the other end is grounded through a resistance equal to its wave impedance. By measuring the voltages at the beginning and at the end of the cable, curves are drawn depending on the ratio of voltages at the end and at the beginning of the cable from the distance between the point of damage and the beginning of the cable, with various degrees of damage to the insulation in it. Using the curves of this dependence α=f(x/l), the location and degree of insulation damage in cables is determined.
PL
Opracowano nową metodę określania miejsca i stopnia uszkodzenia izolacji w kablach. Definiowany jest obwód elektryczny, za pomocą którego wykonywane jest to zadanie. Zgodnie z tym schematem jeden koniec kabla jest podłączony do pulsującego źródła napięcia przez mały opór, a drugi koniec jest uziemiony przez opór równy jego impedancji falowej. Mierząc napięcia na początku i na końcu kabla, rysuje się krzywe w zależności od stosunku napięć na końcu i na początku kabla z odległości pomiędzy miejscem uszkodzenia a początkiem kabla, przy różne stopnie uszkodzenia izolacji w nim. Korzystając z krzywych tej zależności α=f(x/l) określa się miejsce i stopień uszkodzenia izolacji w kablach.
Rocznik
Strony
93--96
Opis fizyczny
Bibliogr. 8 poz., rys., tab.
Twórcy
  • Azerbaijan State Oil and Industry University, Power Faculty, "Electroenergetics" department, Baku, Azerbaijan
  • Azerbaijan State Oil and Industry University, Power Faculty, "Electroenergetics" department, Baku, Azerbaijan
Bibliografia
  • [1] Florkowska B., Florkowski M., Zydroń P., Pomiary i analiza wyładowań niezupełnych w układach izolacyjnych wysokiego napięcia przy narażeniach eksploatacyjnych, Przegląd Elektrotechniczny, 2010, 4, 241-244.
  • [2] Florkowski M., Forkowska B., Rybak A., Zydron P., Migration effects at conductor / XLPE interface subjected to partial discharges at different electrical stresses, IEEE Trans. on Diel. and Electr. Insul., 2015, 22, 456–462
  • [3] A. Shimada, M. Sugimoto, H. Kudoh, K. Tamura, and T. Seguchi, "Degradation distribution in insulation materials of cables by accelerated thermal and radiation ageing", IEEE Transactions on Dielectrics and Electrical Insulation 20, pp. 2107, 2013.
  • [4] A. Shimada, M. Sugimoto, H. Kudoh, K. Tamura, and T. Seguchi, "Degradation mechanisms of silicone rubber (SiR) by accelerated ageing for cables of nuclear power plant", IEEE Transactions on Dielectrics and Electrical Insulation 21, pp.16, 2014.
  • [5] T. Seguchi, K. Tamura, H. Kudoh, A. Shimada, and M. Sugimoto, "Degradation of cable insulation material by accelerated thermal radiation combined ageing", IEEE Transactions on Dielectrics and Electrical Insulation 22, pp. 3197, 2015.
  • [6] Stepanov, V.M. Diagnostics of the technical condition of power cable lines with a voltage of 35-500 kV / V.M. Stepanov, P.A. Borisov // News of TulGU. Technical science. Issue 6. - Part 1. - pp. 66-71, 2011.
  • [7] Gotman V.I. Short circuits and unbalanced modes. Study, for universities. M: Publishing House of Tomsk Polytechnic University, 2013. - 240 p.
  • [8] Lebedev, G.M. Improving the efficiency of operation of 6-10 kV cable lines in power supply systems based on non-destructive diagnostics. / G.M. Lebedev // Moscow Energy Institute. - M., p. 408, 2007.
Uwagi
Opracowanie rekordu ze środków MNiSW, umowa nr SONP/SP/546092/2022 w ramach programu "Społeczna odpowiedzialność nauki" - moduł: Popularyzacja nauki i promocja sportu (2024).
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-7c8c0dbd-c9ef-4749-97d1-e5bac25e6b8b