Single - Point Methods for Location of Electromagnetic Disturbances in Power System

Autorzy
Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Jednopunktowe metody lokalizacji zaburzeń elektromagnetycznych w systemie zasilającym
Języki publikacji
EN
Abstrakty
EN
Often, in the case of a significant level of electromagnetic disturbance in electrical power system, at the customer's supply terminals, there is a need for locating the source of this disturbance, e.g. harmonics, voltage fluctuations, voltage dips, occasionally also asymmetry. Utilities and power consumers have become increasingly interested in quantifying the responsibilities for power quality problems. This issue gains particular meaning when formulating contracts for electric power supply and enforcing, by means of tariff rates, extra charges for worsening the power quality. This paper concerns as an example an application of one method (from the collection of many existing) used to locate sources of electromagnetic disturbances (harmonics, dips, voltage fluctuations and asymmetry), based on the study of the power flow at the point of common coupling (PCC).
PL
Często w przypadku wystąpienia znaczącego poziomu zaburzenia elektromagnetycznego na zaciskach odbiorcy powstaje potrzeba lokalizacji jego źródła, przykładowo harmonicznych, wahań napięcia, zapadów napięcia, niekiedy także asymetrii. Dostawcy i odbiorcy energii w coraz większym stopniu są zainteresowani jednoznaczną oceną odpowiedzialności za złą jakość dostawy energii. Nabiera to szczególnego znaczenia w okresie formułowania kontraktów na dostawę energii i egzekwowania, poprzez taryfy, opłat za pogarszanie jej jakości. W artykule przedstawiono, jako przykład, aplikację jednej metody (ze zbioru wielu istniejących) stosowanej do lokalizacji źródeł zaburzeń elektromagnetycznych (harmonicznych, zapadów, wahań i asymetrii napięcia) opartej na badaniu kierunku przepływu mocy w punkcie wspólnego przyłączenia (PWP).
Rocznik
Strony
1--5
Opis fizyczny
Bibliogr. 59 poz., rys., tab., wykr.
Twórcy
autor
  • Akademia Górniczo-Hutnicza im. S. Staszica, Katedra Energoelektroniki i Automatyki Systemów Przetwarzania Energii, al. Mickiewicza 30, 30-059 Kraków.
Bibliografia
  • [1.] Akagi H., Kanazawa Y., Nabae A.: Generalized theory of instantaneous reactive power in three-phase circuit, Proceedings of the International Power Electronics Conference, Tokyo, Japan, 1983, 1375-1386.
  • [2.] Axelberg P.G.V., Bolen M., Gu L.: A measurement method for determining the direction of propagation of flicker and for tracing a flicker source, International Conference CIRED’2005, Turin (Italy), June 2005.
  • [3.] Axelberg P.G.V., Bollen M.,: An algorithm for determining the direction to a flicker source, IEEE Trans. on Power Delivery, 21, 2, 755-760, 2006.
  • [4.] Axelberg P.G.V., Bollen M., Gu L.: Trace of flicker sources using the quantity of flicker power, IEEE Tran. On Power Delivery, 23, 1, 465-471, 2008.
  • [5.] D’Antona G., Muscas C., Sulis S.: Harmonic source estimation: a new approach for the localization of nonlinear loads, 978- 1-4244- 1 770-4/08, 2008 IEEE.
  • [6.] Bergeron R., Slimani K.: Method for equitable allocation of the cost of harmonics in an electrical network, IEEE Power Engineering Society, Summer Meeting, vol. 1, 1999, pp. 347-353.
  • [7.] Bollen M.H.J.: Understanding power quality problems – voltage sags and interruptions. IEEE Press Series on Power Engineering 2000.
  • [8.] Chang G. W., Chen C. I, Teng Y. F.: An application of radial basis function neural network for harmonics detection, 978-1-4244-1770-4/08,2008 IEEE.
  • [9.] Chen C., Liu X, Koval D.,, Xu W., Tayjasanant T.: Critical impedance method - a new detecting harmonic sources method in distribution systems, IEEE Transactions on Power Delivery, 19, 1, January 2004.
  • [10.] Cristaldi L., Ferrero A.: Harmonic power flow analysis for the measurement of the electric power quality, IEEE Tran. Instrum. Meas, 44, 6,1995, pp. 683-685.
  • [11.] Dán A.M.: Identification of flicker sources, 8th ICHQP ’98, Athens, Greece, Oct. 14-16, 1998.
  • [12.] De Jaeger E.: Measurement of flicker transfer coefficient from HV to MV and LV systems. UIEPQ-9630.
  • [13.] De Jaeger E.: Measurement and evaluation of the flicker emission level from a particular fluctuating load, CIGRE/CIRED Joint Task Force C4.109, Oct. 2007.
  • [14.] De Jaeger E.: Disturbances emission levels assessment techniques (CIGRE/CIRED Joint Working Group C4-109).
  • [15.] Emanuel A. E.: On the assessment of harmonic pollution, IEEE Trans. on Power Delivery, 10, 3, 1995.
  • [16.] Guide to quality of electrical supply for industrial installations. Part 5: Flicker, UIEPQ 1999.
  • [17.] Hamzah N., Mohamed A., Hussain A.: A new approach to locate the voltage sag source using real current component, Electric Power Systems Research, 2004, vol. 72, pp. 113-23.
  • [18.] Hanzelka Z., Słupski P., Piątek K., Varetsky Y., Zielinski M.: Single-point methods for location of distortion, unbalance, voltage fluctuation and dips sources in a power system, InTech, 2011, e-ISBN: 978-953-307-330-9, pp. 157–198.
  • [19.] Hanzelka Z., Firlit A., Chmielowiec K., Świątek B.: New challenges for voltage quality studies, Przegląd Elektrotechniczny, 89 (6), 2013, pp. 17–25.
  • [20.] IEC 61000-3-6: Assessment of emission limits for the connection of distorting instillations to MV, HV and EHV power systems.
  • [21.] IEC 61000-3-7: Assessment of emission limits for the connection of fluctuating installations to MV, HV and EHV power systems.
  • [22.] IEC 61000-3-13: Assessment of emission limits for the connection of unbalanced installations to MV, HV and EHV power systems.
  • [23.] IEC 61000-4-7: Electromagnetic compatibility (EMC) Part 4: Testing and measurement techniques Section 7: General guide on harmonics and interharmonics measurements and instrumentation, for power supply systems and equipment connected thereto.
  • [24.] IEC 61000-4-15: Electromagnetic compatibility (EMC) – Part 4: Testing and measurement techniques – Section 15: Flickermeter – Functional and design specifications.
  • [25.] IEC 61000-4-30: Electromagnetic compatibility (EMC). Part 4. Testing and measuring techniques. Section 30. Measurements of power quality parameters.
  • [26.] IEEE guide for protective relay applications to transmission lines, IEEE Std. C37.113, 1999.
  • [27.] IEEE Power Engineering Society, Distribution System Analysis Subcommitee, IEEE 37 Node Test Feeder
  • [28.] Khosrayi A., Melendez J., Colomer J.: A hybrid method for sag source location in power network, 9th International Conference, Electrical Power Quality and Utilization, Barcelona, 9-lI, October 2007.
  • [29.] Leborgne R.C., Olguin G., Bollen M.: The Influence of PQMonitor Connection on Voltage Dip Measurements, In Proc. 4th Mediterranean IEEE Conference on Power Generation, Transmission, Distribution and Energy Conversion, Cyprus, 2004.
  • [30.] Langley R., Mansoor A.: What causes ASDs to trip during voltage sags? – part 1. Power Quality Assurance, Sep. 1999, 12-15
  • [31.] Li C., Xu W., Tayjasanant T.: A critical impedance based method for identifying harmonic sources, IEEE Transaction on Power Delivery, 19, 1, April 2004.
  • [32.] Li, C., Tayjasanant, T., Xu W., Liu X.: A method for voltage sag source detection by investigating slope of the system trajectory, IEEE Proceedings on Generation, Transmission & Distribution, 150, 3, 2003 pp.367-372.
  • [33.] Nassif A., Nino E., Xu W.: A V-I slope based method for flicker source detection, Annual North American Power Symposium, Edmonton (Canada), October 2005, 0-7803-9255-8/2005 IEEE.
  • [34.] Nasif A., Zhang D., Xu W.: Flicker source identification by interharmonic power direction, IEEE CCECE/CCGEI’2005 International Conference , Saskatoon (Canada), May 2005, 0-7803-8886-0/2005 IEEE.
  • [35.] Nunez V.B., Moliner X.B., Frigola J.M., Jaramillo S.H., Sanchez J., Castro M.: Two methods for voltage sag source location. 13th ICHQP 2008, Australia.
  • [36.] Parsons A. C., Grady W.M., Powers E.J., Soward J.C.: A direction finder for power quality disturbances based upon disturbance power and energy, IEEE Trans. Power Delivery, 2000, 15, 3, pp. 1081-1086.
  • [37.] Pfajfar T., Blaźić B., Papić I.: Methods for estimating customer voltage harmonic emission levels, 978-1-4244-1770-4/08 IEEE.
  • [38.] Polajzer B., Stumberger G., Seme S., Dolinar D.: Generalization of methods for voltage sag-sag source detection using vector-space approach, IEEE Trans. on IA,6,45,2009.
  • [39.] Prakash K. S., Malik O. P., Hope G. S. Amplitude comparator based algorithm for directional comparison protection of transmission lines, IEEE Trans. on Power Delivery, 4, 4, 1989, pp. 2032-2041.
  • [40.] Pradhan A.K. , Routray A.: Applying distance relay for voltage sag source detection, IEEE Trans. on Power Delivery, 20, 2005, pp. 529-31.
  • [41.] Pradhan A.K, Routray A., Madhan S.: Fault direction estimation in radial distribution system using phase change in sequence current, IEEE Tran. on Power Delivery, 22, 2007, pp. 2065-2071.
  • [42.] Pyzalski T., Wilkosz K.: Critical analysis of approaches to localization of harmonic generation, Electrical Power Quality and Utilisation, Cracow, Sep. 17-19, 2003.
  • [43.] Pyzalski T., Wilkosz K.: New approach to localization of harmonic sources in a power system, Electrical Power Quality and Utilisation, Cracow, Sep. 17-19, 2003.
  • [44.] Pyzalski T.: Localization of harmonic sources in a power system, Ph.D. dissertation, Wroclaw University of Technology, 2006.
  • [45.] Review of methods for measurement and evaluation of the harmonic emission level from an individual distorting load, CIGRE 36.05/CIRED 2 Joint WG CCO2, 1998.
  • [46.] Sakulin M.: Flicker measurement - theory and practice. SONT '95 Croatia.
  • [47.] Sakulin M., Renner H., Bergeron R., Hey T., Nastasi D.: International recommendation for universal use of the UIE/IEC flickermeter. UIE/BNCE Birmingham 1996.
  • [48.] Sakulin M.: Flickermeßtechnik. International Conference on Quality of Power and Standardization, June 4-7, 1996, Lohusalli, Estonia.
  • [49.] Stade D. etc.: Simultaneous measurements for analysing the flicker dissipation in meshed HV power systems, 8th ICHQP, Athens, Greece, Oct. 14-16, 1998.
  • [50.] Tayjasanant, T., Li C., Xu W.: A resistance sign-based method for voltage sag source detection. IEEE Tran. on Power Delivery 20, 4, 2005, pp. 2554-2551.
  • [51.] Technical specification, 1133A Power SentinelTM, Arbiter Systems.
  • [52.] The 12th ICHQP Tutorial, Portugal, October 1, 2006.
  • [53.] Tsukamoto M., Kouda I., Natsuda Y., Minowa Y., Nishimura S.: Advanced method to identify harmonics characteristic between utility grid and harmonic current sources, 8th ICHQP, Athens, Greece, Oct. 14-16, 1998.
  • [54.] Varetsky Y., Hanzelka Z.: Negative-sequence active power stream as an index of unbalance source, IEEE EPQU2011 International conference : Lisbon, 17-19 October 2011.
  • [55.] Wilkosz K.: A generalized approach to localization of sources of harmonics in a power system, 13th ICHQP, Australia, 2008.
  • [56.] Wilkosz K.: Metody analizy wyższych harmonicznych w systemie elektroenergetycznym, Oficyna Wydawnicza Politechniki Wrocławskiej, Wrocław 2013.
  • [57.] Xu W., Liu Y.: A method for determining customer and utility harmonic contributions at the point of common coupling, IEEE Trans. on Power Delivery, 15, 2, 2000.
  • [58.] Xu W., Liu X., Liu Y.: An investigation on the validity of power direction method for harmonic source determination, IEEE Trans. Power Delivery, 18, 1, 2003, pp. 214-219.
  • [59.] Zavada F.: Measurement and evaluation of the harmonic emission level from a particular fluctuating load, CIGRECIRED Working Group C4.109, 2008.
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-679228b8-d96b-404e-b494-cd40bef376d9
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.