The sewerage system is a vital component of all wastewater disposal structures. The architecture of buried municipal networks differs significantly depending on the considered city, local subsurface conditions and terrain configuration. History and characterization of sewerage system in Wroclaw which is gravitational with pressure elements (pumping stations, pressure sewers) has been presented. The total length of gravitational sewers equals to ca. 1700 km, including 1300 km combined and separate sanitary sewers as well as 400 km storm water sewers under administration of Wroclaw Municipal Water and Sewerage Systems Company only since 2010. The data about amount of wastewater and recorded failures of gravitational sewers in 2006-2008 have been collated and analyzed. The amount of wastes gathering by combined and separate sanitary sewers was equal to 43-47 million m3per year, and the average indicator of sewage effluent recalculated per one citizen of Wroclaw agglomeration equaled ca. 0.178 m3 per one day. On average per one month, the number of sewers' damages was in the range 7.3-8.3, and the average failure rate per one year and one kilometer of network length (without storm water sewers) equaled 0.07.
Rocznik
Strony
145--157
Opis fizyczny
Bibliogr. 16 poz., tab., rys.
Twórcy
  • Institute of Environment Protection Engineering, Wrocław University of Technology, Wybrzeże Wyspiańskiego 27, 50-370 Wrocław
autor
  • Institute of Environment Protection Engineering, Wrocław University of Technology, Wybrzeże Wyspiańskiego 27, 50-370 Wrocław
Bibliografia
  • 1] KOTOWSKI A., Ochrona Środowiska, 2010, 32 (1), 27.
  • [2] TCHÓRZEWSKA-CIEŚLAK B., Env. Prot. Eng., 2009, 35 (2), 29.
  • [3] RAK J., Env. Prot. Eng., 2009, 35 (2), 23.
  • [4] ZIMOCH I.,Ochrona Środowiska, 2009, 31 (3), 51.
  • [5] BURGSCHWEIGER J.,GNÄDIG B.,STEINBACH M., Optim. Eng., 2009, 10 (1), 43.
  • [6] KWIETNIEWSKI M, RAK J., Reliability of water and sewerage system infrastructure, Polish Academy of Science: Civil and Water Engineering Committee, Warsaw, 2010.
  • [7] RUTSCH M.,RIECKERMANN J.,CULLMANN J., ELLIS J., VOLLERTSEN J., KREBS P.,Wat. Res., 2008, 42 (10–11), 2385.
  • [8] HOTLOŚ H., MIELCARZEWICZ E., Reliability conditions and assessment of a propoer functioning of water-pipe networks and sewer systems in areas affected by mining operations, Oficyna Wydawnicza Politechniki Wrocławskiej, Wrocław, 2011.
  • [9] MADRYAS C., Tunnelling and Underground Space Technology, 2008, 23 (2), 199.
  • [10] Materials from MPWiK in Wrocław, Information collected by repair teams concerning failures occurred in years 2006–2011, Sewerage system damages 2006–2011.xlsx.
  • [11] http://www.mpwik.wroclaw.pl/sub.php?106
  • [12] Materials from MPWiK in Wrocław, 2011, The framework of sewerage system.pdf
  • [13] MPWiK Guidelines for designing and construction. Conditions, standards and requirements, 2011.
  • [14] Materials from MPWiK in Wrocław, 2011, Amount of wastewater in years 1993–2011.xls”
  • [15] KULICZKIWSKI A.,KULICZKOWSKA E., Instal., 2007, 271 (4), 42.
  • [16] PN-EN 13508, The condition of external sewerage systems. Part 1 and 2.