Impact of HTS transformer magnetic circuit parameters on the duration of the inrush current pulse

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Wpływ parametrów obwodu magnetycznego transformatora HTS na czas trwania impulsu prądu włączania
Języki publikacji
EN
Abstrakty
EN
Loss of superconducting state of the superconducting transformer windings shall be treated as an emergency state threatening thermal failure of the circuit continuity. Such a state may occur already at the moment of switching on the transformer due to the inrush current. The value of this current can be many times higher than the critical current of superconducting windings and depends on many factors. The main factor determining the inrush current waveform is the shape of the hysteresis loop of the transformer core. The paper analyses the influence of the basic magnetic parameters of the core on the pulse of the inrush current of the superconducting transformer with attention paid to the phenomenon of the loss of the superconducting state of the windings.
PL
Utratę stanu nadprzewodzenia uzwojeń transformatora nadprzewodnikowego traktuje się jako stan awaryjny grożący termicznym uszkodzeniem ciągłości obwodu. Stan taki może mieć miejsce już w chwili włączania transformatora w skutek wystąpienia prądu włączania. Wartość tego prądu może wielokrotnie przekraczać wartość prądu krytycznego uzwojeń nadprzewodnikowych i zależy od wielu czynników. Głównym czynnikiem decydującym o przebiegu fali prądu włączania jest kształt pętli histerezy rdzenia transformatora. W pracy przeanalizowano wpływ podstawowych parametrów magnetycznych rdzenia na przebieg impulsu prądu włączania transformatora nadprzewodnikowego ze zwróceniem uwagi na zjawisko utraty stanu nadprzewodzenia uzwojeń.
Rocznik
Strony
170--173
Opis fizyczny
Bibliogr. 6 poz., rys. tab.
Twórcy
  • Lublin University of Technology, Institute of Electrical Engineering and Electrotechnologies, Nadbystrzycka 38a, 20-618 Lublin
  • Lublin University of Technology, Institute of Electrical Engineering and Electrotechnologies, Nadbystrzycka 38a, 20-618 Lublin
Bibliografia
  • [1] X. Chen, J. Jin, Development and technology of HTS transformers, Research Communication, vol. 1, no. 1, December 2007.
  • [2] R. A. Turner, K. S. Smith, Transformer inrush currents, IEEE Industry Applications Magazine, vol. 16, no. 5, pp. 14-19, 2010.
  • [3] N. Chiesa, B. A. Mork, H. K. Høidalen, Transformer model for inrush current calculations: simulations, measurements and sensitivity analysis, IEEE Transactions on Power Delivery, vol. 25, no. 4, pp. 2599-2608, 2011.
  • [4] M. Jamali, M. Mirzaie, S. Asghar Gholamian, Calculation and analysis of transformer inrush current based on parameters of transformer and operating condictions, Electronics and Electrical Engineering, Electrical Engineering, 2011, No. 3(109).
  • [5] M. Casali, Experimental analysis and numerical simulation of quench in superconducting HTS tapes and coils, Ph. D. Thesis, University of Bologna, 2014.
  • [6] G. Komarzyniec, 14 kVA superconducting transformer with (RE)BCO windings transformers, 2017 International Conference on Electromagnetic Devices and Processes in Environment Protection with Seminar Applications of Superconductors (ELMECO & AoS), IEEE Conferences, s. 1- 4, Nałęczów, 3-6 grudnia 2017.