Electromagnetic distortion test of renewable energy sources

Treść / Zawartość
Identyfikatory
Warianty tytułu
EN
Badania zaburzeń elektromagnetycznych źródeł energii odnawialnej
Języki publikacji
EN
Abstrakty
EN
The paper presents a number of concerns related to studies of electromagnetic interference produced by renewable energy sources. Firsty, the paper describes types of interference, focusing mainly on impulse disturbances and possible impact on people and the environment. Next, the evaluation methods and measurement equipment are discussed, followed by results of measurements of interference occurring in main power circuits of wind and small hydro-electric power plants. The summary offers recommendations to improve the quality of electricity generated by renewable power sources.
PL
W referacie przedstawiono pewne problemy dotyczące badań zaburzeń elektromagnetycznych wytwarzanych przez odnawialne źródła energii. Na wstępie omówiono rodzaje tych zaburzeń, koncentrując się głównie na zaburzeniach impulsowych oraz przedstawiono możliwe skutki ich oddziaływania dla ludzi i środowiska. Dalej omówiono metody badań zaburzeń oraz stosowane urządzenia pomiarowe. Przedstawiono również przykładowe wyniki pomiarów zaburzeń występujących w obwodach sieci energetycznej generatorów wiatrowych i generatora małej Badania zaburzeń elektromagnetycznych źródeł energii odnawialnej elektrowni wodnej. W podsumowaniu wskazano kierunki dalszych działań dla poprawy jakości energii elektrycznej wytwarzanej przez źródła odnawialne.
Rocznik
Tom
Strony
5--14
Opis fizyczny
Bibliogr. 5 poz., wykr.
Twórcy
autor
  • University of Agriculture in Cracow, Faculty of Production and Power Engineering ul. Balicka 116 b, 30-149 Cracow
autor
  • Tele and Radio Research Institute ul. Ratuszowa 11, 03-450 Warsaw
Bibliografia
  • 1) The frequency range of generated voltage was 49,9 to 50,1 Hz, well within thepermitted range of 50 Hz 1%.
  • 2) Nominal voltage range was within the permitted range, except one instance where the voltage dropped to 125V.
  • 3) During the measurement period, three instances of exceeding the allowed light fluctuation range Plt were encountered. In one case the allowed range was exceeded five-fold.
  • 4) Registered voltage harmonics content was within the permitted range, with 5th and 7th harmonics closest to the maximum allowed. Voltage distortion coefficient THD was also within the permitted range.
  • 5) During the monitored period a large number of pulse-disturbances of the power grid sine wave were detected. The disturbances had a positive or negative polarity and amplitude of up to 500V. Their graphs were consistent with that of dampened oscillations.