In some cases after the superconducting transformer is switched into the energetic network, core saturation occurs. Magnetic field is many times greater than the calculated field. The outer magnetic field causes increase in losses in superconducting transformer’s windings. The effect is getting the windings from superconducting to resistive state. Increase in windings temperature in the resistive state can lead to irreversible superconductor degradation.
PL
W pewnych okolicznościach, włączeniu nieobciążonego transformatora nadprzewodnikowego do sieci towarzyszyć może prąd włączania o dużej wartości. Na skutek nasycenia rdzenia, pole magnetyczne w kolumnie wielokrotnie przekracza wartość obliczeniową. W efekcie może mieć miejsce przekroczenie krytycznych wartości prądu oraz natężenia pola materiału nadprzewodnikowego, uzwojenia transformatora przechodzą ze stanu nadprzewodzenia do stanu rezystywnego. Wzrost strat przekłada się na wzrost temperatury nadprzewodnika, mogący prowadzić do termicznego uszkodzenia uzwojeń. W pracy poddano analizie wzrost strat w uzwojeniu transformatora HTS na skutek przepływu prądu włączania.
Rocznik
Strony
36--39
Opis fizyczny
Bibliogr. 10 poz., schem., tab., wykr.
Twórcy
  • Lublin University of Technology, Institute of Electrical Engineering and Electrotechnologies, ul. Nadbystrzycka 38A, 20-618 Lublin
Bibliografia
  • [1] G. Wojtasiewicz, G. Komarzyniec, J. Janowski, S. Kozak, J. Kozak, M. Majka, B. Kondratowicz-Kucewicz, Inrush Current of Superconducting Transformer, IEEE Transactions on Applied Superconductivity, Volume 23, Issue 3, 2013
  • [2] Z. Spoljaric, V. Jerkovic, M. Stojkov, Measurement system for transformer inrush current higher harmonics determination, Annals & Proceedings of DAAAM International 2012, Vol. 23, No.1, 2012
  • [3] A. Berger, S. Cherevatskiy, M. Noe, T. Leibfried, Comparison of the efficiency of superconducting and conventional transformers, Journal of Physics, Conference Series, volume 234, Part 3, 2010
  • [4] W. Noris, Calculation of hysteresis losses in hard superconductors carrying ac: isolated conductors and edges of thins sheets, J. Phys. D: Appl. Phys. 3 489-507, 1970
  • [5] E. H. Brandt, M. Indenbom, Type-II-superconductor strip with current in a perpendicular magnetic field, Phys. Rev. B 48, 12893, November 1993
  • [6] N. Magnusson, A. Wolfbrandt, AC losses in high-temperature superconducting tapes exposed to longitudinal magnetic fields, Cryogenics 41, 721–724, 2001
  • [7] M. Sjöström, B. Dutoit, and J. Duron, “Equivalent Circuit Model for Superconductors,” IEEE Transactions on Applied Superconductivity, vol. 13, no. 2, June 2003
  • [8] K. V. Namjoshi, P. P. Biringer, Low-frequency eddy-current loss estimation in long conductors by using the moment of inertia of cross sections, IEEE Transactions On Magnetics, Vol. 24, No. 5, September 1988
  • [9] G. Komarzyniec, T. Janowski, G Wojtasiewicz, M. Majka, Thermal problems in HTS transfomer due to inrush current, Przegląd Elektrotechniczny, No. 2, 2014
  • [10] E. Jezierski, Transformatory, WNT, Warszawa 1983
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-430a181c-06b7-4853-bb96-696977477ac2
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.