Classification of leakage current odd harmonic component of aged insulator surface condition under different relative humidity using crest factor

Treść / Zawartość
Identyfikatory
Warianty tytułu
Języki publikacji
EN
Abstrakty
EN
The impact of pollution on insulator surface performance has been extensively studied to continuously improve the insulator performance using suitable condition monitoring, including using the leakage current harmonic component analysis. However, the analysis of harmonic components, particularly in relation to the odd harmonics of the leakage current in aged insulators under the influence of contamination and humidity, is still not fully understood and remains deficient. In this paper, the leakage current of aged and polluted insulators under different environmental conditions are investigated. The study was conducted experimentally using twelve samples of insulators with varying degrees of aging. The crest factor was employed as an indicator of the leakage current index. The findings showed that the odd harmonic crest factor demonstrates high sensitivity in classifying the degree of aging in contaminated insulators.
Rocznik
Strony
1069--1085
Opis fizyczny
Bibliogr. 42 poz., fot., wykr., wz.
Twórcy
  • Institute of High Voltage and High Current, Faculty of Electrical Engineering, University of Technology Malaysia, 81310 Johor Bahru, Malaysia
  • Department of Electrical and Electronics Engineering, Faculty of Engineering, University of Maiduguri, P.M.B 1067 Maiduguri, Nigeria
  • Institute of High Voltage and High Current, Faculty of Electrical Engineering, University of Technology Malaysia, 81310 Johor Bahru, Malaysia
autor
  • Institute of High Voltage and High Current, Faculty of Electrical Engineering, University of Technology Malaysia, 81310 Johor Bahru, Malaysia
Bibliografia
  • [1] Ahmed R. et al., Online Condition Monitoring and Leakage Current Effect Based on Local Area Environment, Trans. Electr. Electro., vol. 21, no. 2, pp. 144–149 (2020), DOI: 10.1007/s42341-020- 00184-1.
  • [2] Nekahi A., McMeekin S., Farzaneh M., Performance comparison of silicone rubber and EPDM insulators in humid and contaminated environments, in 2016 IEEE International Conference on Dielectrics (ICD), IEEE, vol. 2, pp. 712–715 (2016), DOI: 10.1109/ICD.2016.7547715.
  • [3] Banik A., Nielsen S., Nourbakhsh G., Impact of voltage harmonics on condition assessment of polluted insulator through a simulation model, in 2018 Condition Monitoring and Diagnosis (CMD), IEEE, pp. 1–5 (2018), DOI: 10.1109/CMD.2018.8535674.
  • [4] Ramirez-Vazquez I., Fierro-Chavez J.L., Criteria for the diagnostic of polluted ceramic insulators based on the leakage current monitoring technique, in 1999 Annual report conference on electrical insulation and dielectric phenomena (Cat. No. 99CH36319), IEEE, vol. 2, pp. 715–718 (1999), DOI: 10.1109/CEIDP.1999.807905.
  • [5] Bashir N., Ahmad H., Odd harmonics and third to fifth harmonic ratios of leakage currents as diagnostic tools to study the ageing of glass insulators, IEEE Transactions on Dielectrics and Electrical Insulation, vol. 17, no. 3, pp. 819–832 (2010), DOI: 10.1109/TDEI.2010.5492255.
  • [6] Banik A., Nielsen S., Nourbakhsh G., A crest factor-based technique for the analysis of polluted insulator leakage current under harmonically distorted supply voltage, Electr. Eng., vol. 103, pp. 1823–1836 (2021), DOI: 10.1007/s00202-020-01184-3.
  • [7] Pradhan A.K., Chatterjee S., Banik A., Dalai S., Chatterjee B., Condition assessment of outdoor porcelain insulator based on dielectric dissipation factor evaluated from non-linear equivalent circuit, IET Science, Measurement and Technology, vol. 10, no. 8, pp. 866–873 (2016), DOI: 10.1049/ietsmt.2016.0116.
  • [8] Zhao S., Jiang X., Zhang Z., Hu J., Shu L., Flashover voltage prediction of composite insulators based on the characteristics of leakage current, IEEE Transactions on Power Delivery, vol. 28, no. 3, pp. 1699–1708 (2013), DOI: 10.1109/TPWRD.2013.2257879.
  • [9] Ghosh R., Chatterjee B., Chakravorti S., A novel leakage current index for the field monitoring of overhead insulators under harmonic voltage, IEEE Transactions on Industrial Electronics, vol. 65, no. 2, pp. 1568–1576 (2017), DOI: 10.1109/TIE.2017.2733490.
  • [10] Li J., Sima W., Sun C., Sebo S.A., Use of leakage currents of insulators to determine the stage characteristics of the flashover process and contamination level prediction, IEEE Transactions on Dielectrics and Electrical Insulation, vol. 17, no. 2, pp. 490–501 (2010), DOI: 10.1109/TDEI.2010.5448105.
  • [11] Liu Y., Du B., Recurrent plot analysis of leakage current on flashover performance of rime-iced composite insulator, IEEE Transactions on Dielectrics and Electrical insulation, vol. 17, no. 2, pp. 465–472 (2010), DOI: 10.1109/TDEI.2010.5448102.
  • [12] Terrab H., Bayadi A., Experimental study using design of experiment of pollution layer effect on insulator performance taking into account the presence of dry bands, IEEE Transactions on Dielectrics and Electrical Insulation, vol. 21, no. 6, pp. 2486–2495 (2014), DOI: 10.1109/TDEI.2014.004542.
  • [13] Salem A.A. et al., Leakage current characteristics in estimating insulator reliability: experimental investigation and analysis, Scientific Reports, vol. 12, no. 1, 14974 (2022).
  • [14] Reza Ahmadi-Veshki M., Mirzaie M., Sobhani R., Reliability assessment of aged SiR insulators under humidity and pollution conditions, International Journal of Electrical Power & Energy Systems, vol. 117, 105679 (2020), DOI: 10.1016/j.ijepes.2019.105679.
  • [15] Roman M., Van Zyl R., Parus N., Mahatho N., Insulator leakage current monitoring: Challenges for high voltage direct current transmission lines, in 2014 International conference on the eleventh industrial and commercial use of energy, IEEE, pp. 1–7 (2014), DOI: 10.1109/ICUE.2014.6904201.
  • [16] Salem A.A. et al., Risk assessment of polluted glass insulator using leakage current index under different operating conditions, IEEE Access, vol. 8, pp. 175827–175839 (2020), DOI: 10.1109/ACCESS.2020.3026136.
  • [17] Sartika N., Naufalarizqa R., Study on leakage current characteristics and computer simulation of semiconducting glazed insulator under clean and salt fog condition, in 2018 12th International Conference on the Properties and Applications of Dielectric Materials (ICPADM), IEEE, pp. 82–85 (2018), DOI: 10.1109/ICPADM.2018.8401082.
  • [18] Ahmad H., Salam M., Ying L.Y., Bashir N., Harmonic components of leakage current as a diagnostic tool to study the aging of insulators, Journal of Electrostatics, vol. 66, no. 3–4, pp. 156–164 (2008), DOI: 10.1016/j.elstat.2007.11.004.
  • [19] Chandrasekar S., Kalaivanan C., Cavallini A., Montanari G.C., Investigations on leakage current and phase angle characteristics of porcelain and polymeric insulator under contaminated conditions, IEEE Transactions on Dielectrics and Electrical Insulation, vol. 16, no. 2, pp. 574–583 (2009), DOI: 10.1109/TDEI.2009.4815193.
  • [20] El-Hag A.H., Jayaram S.H., Cherney E.A., Fundamental and low frequency harmonic components of leakage current as a diagnostic tool to study aging of RTV and HTV silicone rubber in salt-fog, IEEE Transactions on Dielectrics and Electrical insulation, vol. 10, no. 1, pp. 128–136 (2003), DOI: 10.1109/TDEI.2003.1176575.
  • [21] Kordkheili H.H., Abravesh H., Tabasi M., Dakhem M., Abravesh M.M., Determining the probability of flashover occurrence in composite insulators by using leakage current harmonic components, IEEE Transactions on Dielectrics and Electrical Insulation, vol. 17, no. 2, pp. 502–512 (2010), DOI: 10.1109/TDEI.2010.5448106.
  • [22] Li J., Sun C., Sebo S., Humidity and contamination severity impact on the leakage currents of porcelain insulators, IET generation, transmission and distribution, vol. 5, no. 1, pp. 19–28 (2011), DOI: 10.1049/iet-gtd.2009.0559.
  • [23] Albadi M.H., Al Abri R.S., Al Hinai A.S., Al-Badi A.H., Harmonics temporal profile in high-voltage networks: case study, Power System Harmonics: Analysis, Effects and Mitigation Solutions for Power Quality Improvement, pp. 35–50 (2018), DOI: 10.5772/intechopen.72568.
  • [24] Bashir N., Ahmad H., Leakage current harmonic components: Indexes to insulator ageing, in TENCON 2009-2009 IEEE Region 10 Conference, IEEE, pp. 1–5 (2009), DOI: 10.1109/TENCON.2009.5396216.
  • [25] Benguesmia H., M’Ziou N., Boubakeur A., Experimental study of pollution effect on the behavior of high voltage insulators under alternative current, Front Energy, vol. 15, pp. 213–221 (2021), DOI: 10.1007/s11708-017-0479-1.
  • [26] Cao B., Liu Y., Li Z., Shen S., Wang L., Wang Z., Assessment of insulator pollution degree based on contamination moisture with temperature change, IEEE Sensors Journal, vol. 22, no. 21, pp. 21172–21178 (2022), DOI: 10.1109/JSEN.2022.3206215.
  • [27] Zhang K., Guo X., Xu Y., Research on Insulator Fault in Haze Days Based on Particle Swarm Optimization, in Proceedings of PURPLE MOUNTAIN FORUM 2019-International Forum on Smart Grid Protection and Control, Springer, vol. 1, pp. 287–298 (2020), DOI: 10.1007/978-981-13-9779-0_24.
  • [28] Zhang Z., Qiao X., Xiang Y., Jiang X., Comparison of surface pollution flashover characteristics of RTV (room temperature vulcanizing) coated insulators under different coating damage modes, IEEE Access, vol. 7, pp. 40904–40912 (2019), DOI: 10.1109/ACCESS.2019.2907689.
  • [29] Zhang Z. et al., Study on the dc flashover performance of standard suspension insulator with ring-shaped non-uniform pollution, High Volt, vol. 3, no. 2, pp. 133–139 (2018), DOI: 10.1049/hve.2017.0097.
  • [30] Salem A.A. et al., Pollution flashover voltage of transmission line insulators: Systematic review of experimental works, IEEE Access, vol. 10, pp. 10416–10444 (2022), DOI: 10.1109/ACCESS.2022.3143534.
  • [31] Salem A.A., Abd-Rahman R., Al-Gailani S.A., Kamarudin M.S., Ahmad H., Salam Z., The leakage current components as a diagnostic tool to estimate contamination level on high voltage insulators, IEEE Access, vol. 8, pp. 92514–92528 (2020), DOI: 10.1109/ACCESS.2020.2993630.
  • [32] Khodsuz M., Zamani S.A., Novel criteria for silicone rubber insulators condition monitoring based on leakage current analysis: Considering asymmetric aging and pollution, Engineering Applications of Artificial Intelligence, vol. 133, 108175 (2024), DOI: 10.1016/j.engappai.2024.108175.
  • [33] Banik A., Condition assessment of high voltage insulators in different environments with non-sinusoidal excitation, Queensland University of Technology (2020).
  • [34] Ahmad A.S., Ghosh P.S., Ahmed S.S., Aljunid S.A.K., Assessment of ESDD on high-voltage insulators using artificial neural network, Electric Power Systems Research, vol. 72, no. 2, pp. 131–136 (2004), DOI: 10.1016/j.epsr.2004.03.009.
  • [35] Chakraborty S., Podder S., Deb S., Nath S., Qualitative Analysis of Contamination Severity between NaCl and CuSO4 for Outdoor Insulator, Proceedings of 2018 IEEE Applied Signal Processing Conference (Aspcon), pp. 342–345 (2018), DOI: 10.1109/ASPCON.2018.8748353.
  • [36] Daha M.M., Ibrahim M.E., Izzularab M.A., Effect of Washing Water Flow Rate and Pollution Level on Leakage Current of a Fixed Washed High Voltage Insulator, Proceedings of 2016 Eighteenth International Middle East Power Systems Conference (Mepcon), pp. 234–239 (2016), DOI: 10.1109/MEPCON.2016.7836896.
  • [37] Li J.Y., Sima W.X., Sun C.X., Sebo S.A., Use of Leakage Currents of Insulators to Determine the Stage Characteristics of the Flashover Process and Contamination Level Prediction, IEEE Transactions on Dielectrics and Electrical Insulation, vol. 17, no. 2, pp. 490–501 (2010), DOI: 10.1109/Tdei.2010.5448105.
  • [38] Salem A.A. et al., Effect of pollution distribution scenarioes on flashover characteristics on outdoor insulators, in 2020 IEEE Student Conference on Research and Development (SCOReD), IEEE, pp. 319–324 (2020), DOI: 10.1109/SCOReD50371.2020.9250959.
  • [39] Zhao L., Li C., Xiong J., Wang C., Zhang S., Bi Y., An artificial pollution test on silicone rubber insulators under long-time wetted conditions, in 2007 Annual Report-Conference on Electrical Insulation and Dielectric Phenomena, IEEE, pp. 320–323 2007, DOI: 10.1109/CEIDP.2007.4451559.
  • [40] Salem A., Abd-Rahman R., Ghanem W., Al-Gailani S., Al-Ameri S., Prediction flashover voltage on polluted porcelain insulator using ANN, Comput. Mater. Contin., vol. 68, no. 3, pp. 3755–3771 (2021).
  • [41] Dhahbi-Megriche N., Beroual A., Time–frequency analyses of leakage current waveforms of high voltage insulators in uniform and non-uniform polluted conditions, IET Science, Measurement and Technology, vol. 9, no. 8, pp. 945–954 (2015), DOI: 10.1049/iet-smt.2015.0116.
  • [42] Tian Y., Tie-Yuan X., Rui Z., Jun Z., Bao-Shan W., Study on the frequency spectrum of leakage current for the pollution layer dampness of porcelain post insulator in the pollution test, in 2014 International Conference on Power System Technology, IEEE, pp. 1355–1362 (2014), DOI: 10.1109/POWERCON.2014.6993669.
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-38e1ebfb-a259-4aa3-834c-bf1694322599
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.