PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Dynamic resistance measurements of MV switch-disconnector contacts

Treść / Zawartość
Identyfikatory
Warianty tytułu
PL
Pomiary dynamicznej rezystancji przejścia dla rozłącznika średniego napięcia
Konferencja
XV Seminarium Zastosowanie komputerów w nauce i technice Gdańsk 2015 (XV; 2015, Gdańsk, Polska)
Języki publikacji
EN
Abstrakty
EN
Dynamic Resistance Measurement (DRM) is an effective technique for diagnosing the condition of high power switch contacts. Moreover, the technique can be used to predict the allowable number of switching operations that can be carried out before maintenance of the apparatus is necessary. Since coating materials are characterized by different mechanical and electrical properties, the DRM method can help predict the performance and improve the design of existing high power switches. In this paper both static and dynamic contact resistance measurements for new and worn contact sets of a standard MV switch-disconnector are presented. The contact resistance was measured both in function of the DC injected current magnitude, as well as the number of executed switching operations. The measurements were performed by means of the 4-wire method, and a high speed acquisition digital oscilloscope was used to register the DRM curves.
PL
Pomiar dynamicznej rezystancji styków jest skuteczną metodą diagnostyki stanu aparatu zestykowego. Metoda ta może być wykorzystana do przewidywania możliwej liczby operacji łączeniowych, które mogą być przeprowadzone przed wymaganym przeglądem technicznym urządzenia. Z uwagi na fakt, iż różne materiały stykowe charakteryzują się zróżnicowanymi parametrami mechanicznymi i elektrycznymi, metoda pomiarowa zaprezentowana w artykule może zostać użyta do poprawy istniejących konstrukcji łączników elektroenergetycznych. Niniejszy artykuł przedstawia wyniki pomiarów statycznej oraz dynamicznej rezystancji styku przeprowadzonych dla rozłącznika średniego napięcia. Rezystancję styku zmierzono w funkcji prądu przepływającego przez badany zestyk oraz w funkcji liczby przeprowadzonych operacji łączeniowych, odpowiednio dla nowego i eksploatowanego układu stykowego. Pomiary wykonano przy użyciu czteroprzewodowej metody, z wykorzystaniem cyfrowego oscyloskopu zapewniającego wysoką częstotliwość próbkowania.
Twórcy
  • Corporate Research Centre ABB, Cracow, Poland, tel.: +48 22 223 94 77
autor
  • Corporate Research Centre ABB, Cracow, Poland, tel.: +48 22 223 95 81
autor
  • ABB MV Products Technology Centre, Przasnysz, Poland, tel.: +48 22 223 88 36
autor
  • ABB MV Products Technology Centre, Przasnysz, Poland, tel.: +48 22 223 88 97
Bibliografia
  • [1] Stanisic Z.: Method for Static and Dynamic Resistance Measurements of HV Circuit Breaker, 2nd IEEE PES International Conference and Exhibition on Innovative Smart Grid Technologies (ISGT Europe), Manchester, 5-7 Dec.2011
  • [2] Holm R.: Electric Contacts, Theory and Applications, Berlin, Springer-Verlag, 1967
  • [3] Kassman Rudolphi A.; Jacobson, S.: The contact resistance of rolling silver coated copper contacts, Electrical Contacts, 1997., Proceedings of the Forty-Third IEEE Holm Conference on , pp. 33-40, 20-22 Oct. 1997
  • [4] Khayam U., Risdiyanto A., Suwarno: Reducing Electrical Contact Resistance at Highly Loaded Copper Conductor using Nickel and Silver Coating, 2013 Joint International Conference on Rural Information & Communication Technology and Electric-Vehicle Technology (rICT & ICeV-T), Bandung, 26-28 Nov. 2013
  • [5] Kassman Rudolphi A., Jacobson S.: Gross plastic frettingmechanical deterioration of silver coated electrical contacts, Wear Vol. 201, pp. 244-254, 1996
  • [6] Tingting C., Wenjun Z., Guangyao J., Zhiyong Y., Gao W.: Influence of the Injected Current on Dynamic Contact Resistance Measurements of HV Circuit Breakers, 2014 China International Conference on Electricity Distribution (CICED 2014), Shenzhen, 23-26 Sep. 2014
  • [7] Landry M., Turcotte O., Brikci F.: A complete strategy for conducting dynamic contact resistance measurements on HV circuit breakers, Power Delivery, IEEE Transactions on, vol. 23, pp. 710-716, 2008
  • [8] Landry M., Caron J., Ouellet G., Bastien R.: A new method for measuring the main contact resistance of 25 kV SF Gas FB4-type circuit breakers, the Circuit Breaker Test Maintenance Conf., Jackson, MS, Sep. 6–8, 1999
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-36edeaac-0eb9-4b08-8598-90647c7ea8bd
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.