Impact of Disconnector Design on Insulation Co-ordination in Gas-Insulated UHV Switchgear Substations

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Wpływ konstrukcji odłącznika na obliczenia koordynacji izolacji w gazowych rozdzielnicach najwyższych napięć
Języki publikacji
EN
Abstrakty
EN
Ultra High Voltage (UHV) Gas-Insulated Disconnector Switch is a switching device whose operation is associated with generation of Very Fast Transient Overvoltages (VFTO). As VFTO propagate throughout the substation, they might affect both power equipment, such as bushings and transformers, and also become a dimensioning factor for the UHV GIS elements. In UHV GIS substations a special attention towards VFTO is needed due to the lowered insulation coordination margin for such high voltage levels. In the paper the calculation method is presented which contributes to the accuracy of the VFTO calculation for the insulation coordination analyses. VFTO insulation co-ordination study for exemplary UHV GIS substation is presented. The method presented can lead to more optimized design of the substation elements resulting in more reliable and cost effective solutions.
PL
Odłączniki instalowane w gazowych stacjach najwyższych napięć są złożonymi urządzeniami, których działaniu towarzyszy generowanie przepiąć o najwyższych spotykanych w systemie elektroenergetycznym częstotliwościach. Propagacja tych przepięć powoduje zagrożenie dla urządzeń, jak również stanowi istotne kryterium decydujące o konstrukcji elementów izolacyjnych rozdzielnicy. W artykule przedstawiono metodę pozwalającą na uwzględnienie w analizie koordynacji izolacji rzeczywistych wartości przepięć właściwych dla konstrukcji odłącznika. Wyniki analizy zastosowano do obliczeń przepięć w przykładowym modeli gazowej stacji rozdzielczej najwyższych napięć.
Rocznik
Strony
35--38
Opis fizyczny
Bibliogr. 11 poz., il., tab., wykr.
Twórcy
autor
  • ABB Corporate Research Center, 31-038 Kraków, Starowiślna 13A, Poland
autor
  • ABB Corporate Research Center, 31-038 Kraków, Starowiślna 13A, Poland
autor
  • ABB Corporate Research Center, 31-038 Kraków, Starowiślna 13A, Poland
autor
  • ABB Corporate Research Center, 31-038 Kraków, Starowiślna 13A, Poland
  • ABB Corporate Research Center, 31-038 Kraków, Starowiślna 13A, Poland
autor
  • ABB High Voltage Products, Switzerland
autor
  • ABB High Voltage Products, Switzerland
Bibliografia
  • [1] U. Riechert, U. Krüsi, D. Sologuren-Sanchez, “Very Fast Transient Overvoltages during Switching of Bus-Charging Currents by 1100 kV Disconnector,” CIGRÉ Report 43rd CIGRÉ Session, August 22-27, 2010, Palais des Congrès de Paris, Paris, France A3-107,
  • [2] M. Szewczyk, M. Stosur, W. Piasecki, M. Kuniewski, P. Balcerek, M. Florkowski, U. Riechert, Measurements and Simulations of Very Fast Transients during Disconnector Type Testing in UHV Gas-Insulated Switchgear, Electrotechnical Review (submitted)
  • [3] M. Szewczyk, W. Piasecki, M. Stosur, U. Riechert, J. Kostovic, “Impact of Disconnector Design on Very Fast Transient Overvoltages in Gas-Insulated UHV Switchgear”, Proceedings of 17th International Symposium on High Voltage Engineering (ISH), August 22nd – 26th, Hannover, Germany
  • [4] Development plan , current and future electricity demand in Poland, 2012, Polish Power System Operator
  • [5] K. Johansson, U. Gäfvert, G. Eriksson, L. Johansson, “Modeling and Measurements of VFT Properties of a Transformer to GIS Bushing”, A2.302.2010, CIGRE 2010
  • [6] CIGRE JWG A2-A3-B3.21, “Electrical Environment of Transformers – Impact of Fast Transients”, Electra No. 218, Feb. 2005, pp. 25-37
  • [7] D. Povh, H. Schmitt, O. Volcker, R. Witzmann, P. Chewdhuri, A. E. Imece, R. Iravani, J. A. Martinez, A. Keri, A. Sarshar, “Modeling and Analysis Guidelines for Very Fast Transients”, IEEE Power Engineering Review, Volume: 17, Issue: 13, 1996
  • [8] G. Ecklin, D. Schlicht: “Overvoltages in GIS Caused by the Operation of Isolators”, Proceedings of the Brown Boveri Research Centre, Baden, Switzerland, September 3-4, 1979, pp. 115-128
  • [9] M. Szewczyk, M. Stosur, W. Piasecki, M. Fulczyk, M. Florkowski, M. Steiger, J. Kostovic, "New Disconnector Model for Very Fast Transient Studies in High Voltage Gas Insulated Substations," in Proc. 2010 EEUG (European EMTP-ATP User Group) Conf., pp.154-163
  • [10] IEC 62271-102, “High-Voltage Switchgear and Controlgear – Part 102: Alternating Current Disconnectors and Earthing Switches”
  • [11] H. W. Dommel, W. S. Meyer: “Computation of Electromagnetic Transients,” Proceedings of the IEEE, vol. 62, no. 7, July 1974, pp. 983-993
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-0bf743dc-e779-425a-853f-ee765c67936a
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.