Impact of the receiving transformer on the measurements of long-term load capability of the innovative LV switchgear

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Wpływ transformatora odbiorczego na pomiar obciążalności prądowej długotrwałej innowacyjnej rozdzielnicy niskiego napięcia
Języki publikacji
EN
Abstrakty
EN
This article presents an innovative design of low voltage switchgear and measurements of the long-term current-carrying capacity of the main lines. The functional requirements for the switchgear have been defined for the purposes of powering the equipment and production lines of the domestic pulp and paper production plants. Due to the significant leakage inductance of the installed transformer, the originally planned long-term current-carrying capacity tests failed, therefore a simulation analysis of the influence of the installed transformer on the measurement was carried out.
PL
Niniejszy artykuł przedstawia innowacyjną konstrukcję rozdzielnicy niskiego napięcia oraz pomiary długotrwałej obciążalności prądowej torów głównych. Wymagania funkcjonalne dla rozdzielnicy zostały zdefiniowane na potrzeby zasilania urządzeń i linii produkcyjnych krajowych zakładów wytwórczych branży celulozowo-papierniczej. Z uwagi na znaczną indukcyjność rozproszenia zainstalowanego transformatora nie udały się pierwotnie zaplanowane próby obciążalności długotrwałej prądowej, dlatego przeprowadzono analizę symulacyjną wpływu zainstalowanego transformatora na pomiar.
Rocznik
Strony
186--189
Opis fizyczny
Bibliogr. 8 poz., rys., tab.
Twórcy
  • Warsaw University of Technology, Electrical Power Engineering Institute, ul. Koszykowa 75, 00-662 Warsaw, Poland
  • Warsaw University of Technology, Electrical Power Engineering Institute, ul. Koszykowa 75, 00-662 Warsaw, Poland
  • Warsaw University of Technology, Electrical Power Engineering Institute, ul. Koszykowa 75, 00-662 Warsaw, Poland
  • Warsaw University of Technology, Electrical Power Engineering Institute, ul. Koszykowa 75, 00-662 Warsaw, Poland
  • Elektroteam Sp. z o.o., ul. Brzozowa 8A, 97-400 Bełchatów
Bibliografia
  • [1] Kilindjian C. and Schneider Electric, Cahier technique no. 145: Thermal study of LV electric switchboards, 1997
  • [2] Ryfa A., Buliński Z., Smolka J., Bedkowski M., Burzyński R., Determination of busbar system heat losses in naturally ventilated and hermetic switchgear, IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 7, pp. 1652-1660, doi: 10.1049/ietgtd. 2016.0760
  • [3] Xia H., Guan Y., Yu Z., Cai S., Wang X., Peng Z., Gao S., Huang A., Temperature rise test and analysis oh high current switchgear in distribution system, J. Eng., 2019, Vol. 2019 Iss. 16, pp. 754-757, doi: 10.1049/joe.2018.8371
  • [4] Wang L., Li X., Lin J., Jia S., Studies of Modeling and Simulation Method of Temperature Rise in Medium-Voltage Switchgear and Its Optimum Design, IEEE Trans. On Comp, Pack,and Manufa. Tech., vol. 8, no. 3., 2018
  • [5] Wang L., Wang R., Li X., Yan C., Temparature Rise Simulation of Medium Voltage Cubic Type Gas Insulated Switch-Gear Based on Coupling of Multi-Phisical Field, IEEE Access, vol. 7, 2019, doi: 10.1109/ACCESS.2019.2908993
  • [6] T. Kądziołka, M. Kryś, A. Wiertek, Analysis of power loss and temperature distribution in low voltage switchgear – coupled analysis EM + CFD in ANSYS software, Przegląd Elektrotechniczny, 94 (2018), No 1
  • [7] Będkowski M., Smołka J., Nowak A., Analiza numeryczna procesu wymiany ciepła wewnątrz rozdzielnicy elektrycznej, Przegląd Elektrotechniczny, vol. 2, 2013
  • [8] PN-EN 61439-1:2011 Low-voltage switchgear and controlgear assemblies - Part 1: General rules