Synchronous generator for induced AC voltage test of single-phase and three-phase power transformers

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Generator synchroniczny do prób napięciem indukowanym jedno- i trójfazowych transformatorów mocy
Języki publikacji
EN
Abstrakty
EN
The paper presents the method of selection, calculation and measurements of generator that is built into the new transformer test station. The three phase cylindrical synchronous generator 800 kVA, 200 Hz with special damper bars is most suitable to be used as a power supply for testing of single-phase and three-phase power transformers. The emphasis is on the analysis of the armature winding connection and sizing of the damper winding due to unsymmetrical load of a generator in the induced AC voltage test. The results indicate that D-connected generator with skewed stator slots is the best solution. Special temperature sensors were mounted in the rotor.
PL
W artykule przedstawiono metodę wyboru, obliczeń oraz pomiarów generator wbudowanego w nową transformatorową stację badawczą. Trójfazowy cylindryczny generator trójfazowy o mocy 800 kVA i częstotliwości 200 Hz ze specjalną szyną tłumiącą jest najdogodniejszy jako urządzenie zasilające do prób transformatorów jedno- i trójfazowych. Szczególną uwagę zwrócono na połączenie uzwojeń i wielkość uzwojenia tłumiącego z powodu niesymetrycznego obciążenia generatora w przypadku próby indukowanym napięciem. Wyniki wskazują na to, że generator z uzwojeniami połączonymi w trójkąt i skoszonymi żłobkami statora jest rozwiązaniem najlepszym. Specjalne czujniki temperatury zostały zamontowane w wirniku.
Rocznik
Strony
141--144
Opis fizyczny
Bibliogr. 5 poz., rys., tab., wykr.
Twórcy
  • University of Zagreb, Faculty of Electrical Engineering and Computing, Department of Electric Machines, Drives and Automation, Unska 3, HR-10000 Zagreb, Croatia
autor
  • University of Zagreb, Faculty of Electrical Engineering and Computing, Department of Electric Machines, Drives and Automation, Unska 3, HR-10000 Zagreb, Croatia
Bibliografia
  • [1] Harlow J .H., “Transformers” The Electric Power Engineering Handbook, Ed. L. L. Grigsby, Boca Raton: CRC Press LLC, (2001)
  • [2] Carlson A., Fuhr J., Schemel G., Wegscheider F. , Testing of Power Transformer, Pro Print GmbH, Dusseldorf, pp. 1-293, (2006)
  • [3] IEC 60076-3 Power transformers – Part 3: Insulation levels, dielectric tests and external clearances in air (2000)
  • [4] Maljković Z., Žarko D., Stipetić S. Unsymmetrical load of a three-phase synchronous generator, Przegląd Elektrotechniczny, 89 (2013), nr 2b/2013, 68-71
  • [5] Bingyi Z., Yisong Z., Yong Y., Chang G., Guihong F. , A novel integrated single phase synchronous generation unit for power transformer local discharge test, Proceedings of the Eighth International Conference on Electrical Machines and Systems, ICEMS vol.2 (2005), pp.1024,1026
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-0649969b-a657-4b86-bbfc-4958f1ef4b0a
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.