Narzędzia help

Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
first previous next last
cannonical link button

http://yadda.icm.edu.pl:80/baztech/element/bwmeta1.element.baztech-article-BPS3-0025-0055

Czasopismo

Przegląd Elektrotechniczny

Tytuł artykułu

The Characteristics of Partial Discharge on Corona Defect in GIS based on Multi-Detection method

Autorzy Kou, X.  Li, J.  Yang, J., Li, Y. 
Treść / Zawartość http://pe.org.pl/
Warianty tytułu
PL Badanie różnymi metodami wyładowania niezupełnego w przełącznikach gazowych
Języki publikacji EN
Abstrakty
EN Gas insulated switchgear (GIS) is the most important equipment in the power grid. The partial discharge (PD) is the premonitory detection method for the insulation failure. The UHF detection method and acoustic detection method is the most used in filed. UHF method has excellent antiinterference performance and acoustic method has excellent defect location ability. Metal tip defect will appear on GIS for manufacturing and other reasons. The metal tip will lead to corona discharge under operating voltage. It is necessary to study the characteristics of corona discharge for fault detection and diagnosis. The experimental system is set up and the corona discharge characteristics on conductor and ground in actual GIS model are studied using above two methods. The comparing of the two methods is studied in this paper.
PL Wyładowanie niezupełne może być metodą detekcji złej izolacji w przełącznikach gazowych GIS. Doi wykrywania wyładowania najczęściej używa się metody UHV lub akustycznej. Pierwsza z nich jest odporna na zakłócenia druga bardzo dobrze pozwala na lokalizację wyładowania. W artykule przedstawiono porównanie obu metod. (Badanie różnymi metodami wyładowania niezupełnego w przełącznikach gazowych)
Słowa kluczowe
PL przełącznika gazowy GIS   wyładowanie niezupełne  
EN GIS   corona   UHF   acoustic  
Wydawca Wydawnictwo SIGMA-NOT
Czasopismo Przegląd Elektrotechniczny
Rocznik 2012
Tom R. 88, nr 10a
Strony 176--179
Opis fizyczny Bibliogr. 8 poz., rys.
Twórcy
autor Kou, X.
autor Li, J.
autor Yang, J., Li, Y.
  • State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, xjtuhvljh@gmail.com
Bibliografia
[1] Sabot A, Petit A, Taillebois JP. GIS insulation co-ordination: on-site tests and dielectric diagnostic techniques. A utility point of view[J]. Power Delivery, IEEE Transactions on, 1996, 11 (3): 1309-1316..
[2] Judd MD,Farish O,Hampton BF. The excitation of UHF signals by partial discharges in GIS[J]. Ieee Transactions on Dielectrics and Electrical Insulation,1996,3 (2): 213-228.
[3] Yoshikazu Shibuya, Satoshi Matsumoto, Masayoshi Tanaka, etc. Electromagnetic waves from partial discharges and their detection using patch antenna[J]. Ieee Transactions on Dielectrics and Electrical Insulation,2010,17(3): 862-871.
[4] Lundgaard LE, Runde M, Skyberg B. Acoustic Diagnosis Of Gas Insulated Substations - A Theoretical And Experimental Basis[J]. Ieee Transactions on Power Delivery, 1990, 5 (4): 1751-1759.J. Clerk Maxwell, A Treatise on Electricity and Magnetism, 3rd ed., vol. 2. Oxford: Clarendon, 1892, pp.68–73.
[5] Lundgaard LE. Partial discharge XIII. Acoustic partial discharge detection-fundamental considerations[J]. IEEE Electrical Insulation Magazine, 1992, 8 (4): 10.1109/1157.145095..
[6] Lundgaard LE. Particles in GIS - Characterization from acoustic signatures[J]. Ieee Transactions on Dielectrics and Electrical Insulation, 2001, 8 (6): 1064-1074..
[7] R. E. James and B. T. Phung. Development of computerbased measurements and their application to PD pattern analysis. IEEE Trans. on Dielectrics and Electrical Insulation [J], 1995, 2 (5): 838~856.
[8] R. J. Van Brunt. Stochastic properties of partial-discharge phenomena. IEEE Trans. on Electrical Insulation [J], 1991, 26(5): 902~948.
Kolekcja BazTech
Identyfikator YADDA bwmeta1.element.baztech-article-BPS3-0025-0055
Identyfikatory