Simplified method for computing reactance in the design of saturated-core superconducting fault current limiter

Autorzy Jia, Y.  Hao, L.  Shi, Z.  Zhu, H.  Yuan, J. 
Treść / Zawartość http://pe.org.pl/
Warianty tytułu
EN Uproszczona metoda obliczania reaktancji w projektowaniu nadprzewodzącego ogranicznika prądu z nasyconym rdzeniem
Języki publikacji EN
Abstrakty
EN Generally, the computation of the steady-state reactance of the SCSFCL employs the nonlinear steel core model with both the DC and AC excitation. Noting the deep saturation region of the B-H curve is nearly a straight line, a simplified method is presented in this paper. The slope of the deep saturation region of the B-H curve is taken as an equivalent permeability for the core. Furthermore, the computation can be simplified as a static-magnetic-field model when ignoring the eddy current effect. The example shows this simplified method meets the engineering requirements.
PL Obliczenia reaktancji SCSFCL wymaga użycia nieliniowego modelu rdzenia stalowego zarówno dla wzbudzenia stałoprądowego jak i zmiennoprądowego. W artykule przedstawiono uproszczoną metodę obliczania reaktancji zakładając, że w obszarze dużego nasycenia krzywa B-H jest prawie linią prostą. Jako przenikalność rdzenia przyjęto nachylenie krzywej B-H w obszarze głębokiego nasycenia. Ponadto, obliczenia mogą być uproszczone przez pominięcie prądów wirowych i przyjęcie modelu statycznego. Przykład pokazuje, że metoda uproszczona spełnia wymagania inżynierskie.
Słowa kluczowe
PL przenikalność dynamiczna   projektowanie reaktancji   rdzeń nasycony   nadprzewodzący ogranicznik prądu zwarciowego  
EN dynamic permeability   reactance design   saturated core   superconducting fault current limiter  
Wydawca Wydawnictwo SIGMA-NOT
Czasopismo Przegląd Elektrotechniczny
Rocznik 2016
Tom R. 92, nr 4
Strony 10--13
Opis fizyczny Bibliogr. 8 poz., rys., tab., wykr.
Twórcy
autor Jia, Y.
  • Tsinghua University, West Main Building 1- 302, Tsinghua University, Beijing 100084 China, rhinestone@163.com
autor Hao, L.
autor Shi, Z.
  • Guangdong Power Grid Corporation, Grid Planning & Research Centre, Guangdong Power Grid Corporation, Guangzhou 510600 China, shizhengjun@gd.csg.cn
autor Zhu, H.
  • Guangdong Power Grid Corporation, Grid Planning & Research Centre, Guangdong Power Grid Corporation, Guangzhou 510600 China, zhuhaojun@gd.csg.cn
autor Yuan, J.
  • Tsinghua University, West Main Building 1-302, Tsinghua University, Beijing 100084 China, yuan@tsinghua.edu.cn
Bibliografia
[1] Y. Cai, S. Okuda, and et al., Study on Three-Phase Superconducting Fault Current Limiter, IEEE Trans. Appl. Supercond., 20 (2010), No. 3, pp. 1127-1130.
[2] L. Ye, M. Majoros, and et al., System Studies of the Superconducting Fault Current Limiter in Electrical Distribution Grids, IEEE Trans. Appl. Supercond, 17 (2007), No. 2, pp. 2339-2342.
[3] H. Kang, C. Lee, and et al., Development of a 13.2 kV/630 A (8.3 MVA) High Temperature Superconducting Fault Current Limiter, IEEE Trans. Appl. Supercond., 18 (2008), No. 2, 628-631.
[4] J. Cui, B. Shu, and et al., Safety Considerations in the Design, Fabrication, Testing, and Operation of the DC Bias Coil of a Saturated Iron-Core Superconducting Fault Current Limiter, IEEE Trans. Appl. Supercond. , 23 (2013), No. 3, 5600704.
[5] Y. Pan, M. Steurer, and et al., Impact of Waveform Distorting Fault Current Limiters on Previously Installed Overcurrent Relays, IEEE Trans. Power Delivery, 23 (2008), No. 3, 1310-1318.
[6] A. Abramovitz, K. Smedley, and et al., Prototyping and Testing of a 15 kV/1.2 kA Saturable Core HTS Fault Current Limiter, IEEE Trans. Power Delivery, 28 (2013), No. 3, 1271-1279.
[7] Y Nikulshin, Y Wolfus, and et al., Dynamic core length in saturated core fault current limiters, Superconductor Science and Technology, 26 (2013), No. 9, 095013.
[8] C. Zhao, S. Wang, and et al., Transient Simulation and Analysis for Saturated Core High Temperature Superconducting Fault Current Limiter, IEEE Trans. Magn., 43 (2002), No. 4, 1813-1816.